Operation
33722 D MMG130DI4/175DI4/205DI4 Operating Manual 25
AUTO (REMOTE) STARTING OF THE UNIT
Auto mode is used when the unit is started from a location other than the control panel by using a transfer switch.
Auto (remote start) is the normal setting when the unit is being used as a standby power supply. Before putting the
unit in the Auto mode, review the Prestart Checklist and Manually Starting the Unit. Also follow all safety warnings
and information on isolating the generator with a transfer switch if the unit is to be used as a standby power supply.
Refer to Transfer Switch. Then continue with the steps described below:
1. Perform a manual start of the unit at least once to verify that the engine is operating correctly.
2. If a check of the remote start circuit is desired, remove the wires from the remote start terminal block. Press
the Auto/Manual Mode ( ) button, the LCD window should show “Auto Mode” at the top of the screen.
Attach a jumper wire (minimum 16 gauge) across the two terminals on the remote start terminal block. This
applies a ground to the Power Zone™ Controller to close the starting circuit contacts. The engine should
crank, start and run.
3. Remove the jumper wire from the remote start terminal block and the engine will stop. Reconnect any nec-
essary wires from the remote start switch (transfer switch) to the remote start terminal block.
4. Confirm the unit is in Auto mode. The LCD window should show “Auto Mode” at the top of the screen.
5. Close the main circuit breaker (set to ON (I)).
6. Secure the unit by closing and locking all access doors.
7. The unit is now ready for remote starting.
The remote start terminal block provides a connection for installation of a remote start
switch which will allow the unit to be started by a remote dry-contact closure switch.
For location of the remote start terminal block, refer to Control Panel.
Before entering Auto mode, verify that the contacts on any remote switch linked to the
unit are OPEN. If the contacts on a remote switch are closed, the engine will crank
and start when Auto mode is entered. Attach the switch leads to the two unused
terminals on the unit’s remote start terminal block.
Figure 3-3. Remote Start
Terminal Block
DERATING FOR ALTITUDE
All units are subject to derating for altitude and temperature; this will reduce the available power for operating tools
and accessories connected to the receptacles. Typical reductions in performance are 2-4% for every 1000 ft (305
m) of elevation and 1% per 10ºF (5.6ºC) increase in ambient air temperature over 72ºF (22ºC).
GENERATOR OUTPUT CONNECTIONS
The unit is equipped with connection lugs, located on the lower portion of the control box behind the lug box door.
The lugs provide connection points for attachment of external loads to the generator. A large decal on the inside of
the connection lug door details the proper connections for selected voltages.
WARNING
It is HIGHLY RECOMMENDED that only a trained and licensed electrician perform any
wiring and related connections to the generator. Installation should be in compliance
with the National Electrical Code (NEC), state and local regulations. Failure to follow
proper installation requirements may result in equipment or property damage, per-
sonal injury, or death.
Remote Start
Switch Terminals
00231
31


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Generac MMG175DI4 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Generac MMG175DI4 in the language / languages: English as an attachment in your email.

The manual is 4,87 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info