DSX CableAnalyzer
Users Manual
30
Set the Reference
The reference procedure for twisted pair cable sets the baseline
for insertion loss, ACR-F, and DC resistance measurements.
Set the reference at these times:
When you want to use the tester with a different remote. You
can set the reference for eight different remotes.
When you attach Class F/F
A
link interface adapters, such as the
optional DSX-PLA011 TERA
adapters.
Every 30 days. This ensures maximum accuracy of test results.
It is not necessary to set the reference when you change the link
interface adapters.
To set the reference
1 Turn on the tester and the remote a minimum of 1 minute
before you set the reference.
Note
Set the reference only after the testers are at an
ambient temperature between 50 °F and 104 °F
(10 °C and 40 °C).
2 Connect the main and remote testers together as shown in
Figure 12.
3 If you attached Class F/F
A
link interface adapters, make sure
you select a Class F or F
A
test limit. See the documentation
supplied with the adapters.
4 On the home screen, tap TOOLS, then tap Set Reference.
5 On the SET REFERENCE screen tap TEST.
riešenia na presné meranie
http://www.elso.sk
38


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Fluke networks DSX CableAnalyzer at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Fluke networks DSX CableAnalyzer in the language / languages: English as an attachment in your email.

The manual is 7 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Fluke networks DSX CableAnalyzer

Fluke networks DSX CableAnalyzer Quick start guide - English - 10 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info