190 Series III
Users Manual
66
Motor Drive DC-Bus
The Motor Drive DC-Bus functions check the intermediate circuit of the motor drive.
XW Warning
To prevent possible electrical shock, fire, or personal injury, be aware that the
voltage that is present on the dc bus outputs remains on these outputs after the
motor drive is turned off. The amount of time depends on the internal impedance.
Voltage DC Level
The Voltage DC Level checks the value and stability of the internal DC-bus of the drive and
influence of braking or power feedback (if supported by the drive).
The readings show the dc level, as well as, the peak and peak-peak value. Use Voltage AC
Ripple for a closer look at the ac component.
The dc bus voltage should be about 1.414 times the rms line voltage, except when controlled
rectifiers (IGBT) are used in the input section. A dc voltage that is too low can trip the drive. Low
voltage can be caused by low input mains voltage or distorted input voltage by flat topping.
Tips:
Use the RECORD function to check the dc voltage stability over time and detect slow
fluctuations. The test tool continuously records the digital readings of the measurements and
displays these as a graph.
The TrendPlot graph rolls from right to left like a paper chart recorder. Observe that the
recorded time from start appears at the bottom of the screen. The present reading appears on
top of the screen.
Voltage AC Ripple
The Voltage AC Ripple function detects rapid fluctuations and ac components on the dc-bus.
Tips:
A slight ripple can be visible and is load dependent. If the peaks of ripple have a different
repetitive level, one of the rectifiers could be malfunctioning.
Ripple voltages >40 V can be caused by malfunctioning capacitors or the drive rating is too
small for the connected motor and load.
72


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Fluke MDA-550-III at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Fluke MDA-550-III in the language / languages: English as an attachment in your email.

The manual is 9.23 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info