Clamp Meter
Basic Measurements
11
Basic Measurements
XW Warning
To prevent possible electrical shock, fire, or
personal injury:
Hold the Product behind the tactile barrier.
Do not measure current while the test leads are
in the input jacks.
Note
Exposure to severe mechanical shock may cause the
readings of the Product to not meet the specifications.
If the published accuracy is required, the Product
should be calibrated to verify proper operation after
such an event. See Service.
Hazardous Voltage Indicator
When the Clamp senses a voltage ±30 V or a voltage overload
(OL), Z shows on the display to tell you a hazardous voltage is at
the Clamp input.
FieldSense™ Measurement
FieldSense measurement, or non-contact voltage (NCV)
measurement, is ac voltage, current, and frequency measurement
with no electrical contact to live voltage. The Clamp display shows
the voltage and current measurements at the same time.
Note
All FieldSense measurements require a ground lead
connection.
FieldSense AC Current, Voltage, and Frequency
To make the measurement:
1. Insert the ground lead into the COM input and attach the
alligator clip to ground.
2. Rotate the control knob to U.
The display shows the U icon.
3. Use the jaw release to open the jaw and position the Clamp
around the conductor. Close the jaw and make sure the wire
position is correct. See Figure 2.
Figure 2. Wire Placement
The display shows C to indicate that the measurement is
from the jaw. When the current measurement is <0.5 A, the
center dot in the icon flashes. For current measurements
>0.5 A, the center dot in the icon is steady. The Aac display
shows - - - when a measurement is <1 A.
Note
Use B to toggle on/toggle off the Amps Hz function
shown in yellow at the control knob position.
FieldSense technology is not intended to measure the
output of a variable-frequency drive (VFD) motor
controller. Use the V or Kcontrol knob position for
this application.
34 mm Ø
3.3 mm Ø
L1 L2 L3
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Fluke 378 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Fluke 378 in the language / languages: English as an attachment in your email.

The manual is 2,02 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Fluke 378

Fluke 378 User Manual - German - 22 pages

Fluke 378 User Manual - Dutch - 22 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info