775830
78
Zoom out
Zoom in
Previous page
1/98
Next page
190 Series III
Users Manual
72
6. Use one of the ground leads to contact the motor chassis that is the reference ground.
When it is not possible to connect near the shaft, an extension cord with 4 mm connections
on both ends is included for extending the connection to the ground lead. The measurement
can be done on the driven and the non-driven end of the motor.
7. Turn on the motor.
8. Do the measurement after the motor warms up to normal operating temperature.
With this function you can determine the number of flash-overs that occur between shaft and
motor chassis, also referred to as electrical discharge machining. When motor shaft voltages
exceed the bearing grease insulation capability, flash-over currents occur and cause pitting
and grooving of the bearing races.
Tips:
Under direct 50/60 Hz mains operation, the shaft voltage is normally <1 V.
Due to the fast edges of the switching voltage from a motor drive, the shaft voltage for a
motor powered by a motor drive can be much higher. High Voltage can cause large
breakdown currents across the grease barrier causing damage to the bearings.
Normal, unavoidable shaft voltage due to asymmetry in the air-gap magnetic field result in
peak voltages <5 V and slower than 100 ns, which, in general, are not damaging.
Voltage discharges of >15 V and transition times faster than 50 ns can point to grease flash-
over currents that can damage bearings. However, no fixed values can be given that can be
considered damaging for the motor, as there are many factors that influence this value.
After selecting the Motor Shaft Voltage measurement, the display shows the voltage waveform.
The voltage peak-peak reading shows at the top of the display. Select 2 EVENTS ON to
view the discharge event and count the amount of discharge events. Only the discharge events
show. The readings at the top of the display show the Volt Peak-Peak, dV/dt, and falltime or
risetime as well as the number of events/second. Expect about 20 seconds before the number of
events/second shows on the display.
Use 4 DEFINE EVENTS to define what is considered a discharge event.
In this screen, select the maximum voltage change and maximum rise or fall time that will be
counted and displayed as an event.
Tips:
No waveform is visible when no events are detected.
If excessive shaft voltage is measured, check that the voltage discharges can be reduced by
adapting the cabling, grounding, drive parameters, or lubricant. If this is not possible or does
not help, use the shaft grounding devices or the isolated shaft.
If a bearing runs hot or is noisy and high shaft voltages are measured, bearing flash-over
currents can be the primary source of excessive bearing wear.
Check other sources of bearing wear, such as, coupling misalignment or looseness.
78


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Fluke 190-502-III at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Fluke 190-502-III in the language / languages: English as an attachment in your email.

The manual is 9.23 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info