3 Phase Power Quality Analyzer
Measurement Configuration
29
Event Trigger Settings
The capture of events requires trigger settings. A set of standard settings are enabled by
default. These triggers are to specify when a detailed RMS capture occurs in the Analyzer. The
1775 and 1777 models also include a waveform and transient capture as well as the detailed
RMS voltage capture.
The available settings are:
Dip
Swell
Interruption
Waveshape Deviation
Transients
Rapid Voltage Change
Inrush Current
For more details about each of these event settings, see Glossary.
Dips and Swells. For dips and swells the capture is based on the RMS voltage expressed as a
percentage of the nominal voltage.
The defaults for these settings are 90 % and 110 %. This means that for a 230 V nominal the
voltage must drop by 23 V to capture, and a swell capture is triggered at 253 V. Hysteresis of
2 % is automatically assumed, this means that the event is considered to have ended if the 2 %
recovery within 90 % or 110 % of voltage is made. This setting ensures that multiple events are
not captured for a single event. The setting of this voltage is considered from a standard
averages period of 200 ms or a sliding reference is applied. This reference considers the last
10 cycles for 50 Hz or 12 cycles for 60 Hz.
Use a sliding reference where the nominal voltage can vary more freely. This is usually the case
in high voltage systems. When you apply the sliding reference, the Analyzer detects dips and
swells based on a voltage change relative to the actual rms voltage, rather than, the absolute
nominal voltage.
Interruptions. Interruptions are events when a total power loss is made at the load across all
measured phases. This could be a blown fuses, a breaker tripping, or utility power loss. In the
case of power loss, the default value is 5 % of the nominal voltage. You can increase this
voltage if the registration of the interruption is not correctly represented or if the electrical
system is supported for several cycles by inductive or capacitance effects in the system. An
automatic hysteresis of 2 % is applied.
Waveshape Deviation. The deviation of the waveform considers the consecutive waveform
based on sample-to-sample comparison of the waveform. The trigger starts when the
magnitude of each cycle is compared with the sample magnitude on the next cycle. This is
expressed as a percentage of the nominal voltage. The default setting is 10 % of voltage. To
activate this trigger, check the Trigger On box.
35


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Fluke 1777 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Fluke 1777 in the language / languages: English as an attachment in your email.

The manual is 3.36 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info