6.2 TROUBLESHOOTING
The troubleshooting and the eventual checks have to be worked out by qualified personnel. Pay
particular attention in case of interventions on the refrigerating circuit. The refrigerating fluid, if
under pressure, while expanding could cause freezing burns and serious damage to the eyes,
should it get in contact with them.
SYMPTOM POSSIBLE CAUSE - SUGGESTED ACTION
The dryer doesn't start. Check for mains failure.
Verify the electric wiring.
The compressor doesn’t
work.
Activation of the compressor internal thermal protection - wait for 30
minutes, then retry.
Verify the electric wiring.
Replace the internal thermal protection of the compressor.
If the compressor still doesn’t work, replace it.
The fan of the condenser
doesn’t work.
Verify the electric wiring.
Pv pressure switch is faulty - contact a refrigeration engineer.
If the fan still doesn’t work, replace it.
DewPoint too high. The dryer doesn't start - see specific point.
The DewPoint probe doesn’t correctly detect the temperature - ensure the
sensor is pushed into the bottom of copper tube immersion well.
The condenser is dirty - clean it.
The dryer doesn’t drain the condensate - see specific point.
The ambient temperature is too high or the room aeration is insufficient -
provide proper ventilation.
The inlet air is too hot - restore the nominal conditions.
The condenser fan doesn’t work - see specific point.
The refrigerating compressor doesn’t work - see specific point.
The hot gas by-pass valve is out of setting - contact a refrigeration engineer
to restore the nominal setting.
There is a leak in the refrigerating fluid circuit - contact a refrigeration engineer.
The inlet air pressure is too low - restore the nominal conditions.
The inlet air flow rate is higher than the rate of the dryer - reduce the flow
rate - restore the normal conditions.
DewPoint too low. The fan is always ON - Pv pressure switch is faulty - replace it.
The hot gas by-pass valve is out of setting - contact a refrigeration engineer
to restore the nominal setting.
Excessive pressure drop
within the dryer.
The FS 018 Inlet filter - 1 micron is clogged - replace the cartridge.
The dryer doesn’t drain the condensate - see specific point.
The DewPoint is too low - the condensate is frost and blocks the air - see
specific point.
Check for throttling the flexible connection hoses (if installed).
The dryer doesn’t drain
the condensate.
The condensate drain service valve is closed - open it.
The condensate drain mechanical strainer is clogged - remove and clean it.
The drain solenoid valve is jammed - remove and clean it.
Verify the electric wiring.
The coil of the condensate drain solenoid valve burned out - replace it.
The DewPoint is too low - the condensate is frozen - see specific point.
The DTT11 Electronic Instrument is faulty - replace it.
The dryer continuously
drains condensate.
The drain solenoid valve is jammed - remove and clean it.
Try to remove the electric connector on the solenoid valve - if drain stop the
DTT11 Electronic Instruments is faulty - replace it.
Water within the line. The dryer is OFF - switch it ON.
Untreated air flows through the by-pass group - close the by-pass.
The dryer doesn’t drain condensate - see specific point.
DewPoint too high - see specific point.
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Finicompressors Artic 134-EVO luchtdroger at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Finicompressors Artic 134-EVO luchtdroger in the language / languages: English as an attachment in your email.

The manual is 1,04 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info