7
Test
Immediately after activation, testing is necessary. Test the unit to ensure proper
operation by pressing the test button for at least 5 seconds, which will cause the alarm
to sound if the electronic circuitry, horn and battery are working properly. If there is no
alarm, the battery is defective or there is some other malfunction. Refer to the
"Troubleshooting" section for a solution.
Do NOT use an open flame to test your alarm, you could damage the alarm or ignite
combustible materials and cause a fire.
WARNING: Because of the sound volume (85 decibels) of the alarm, you should always
stand at arm's length away from the unit during testing. An irregular or low sound
volume of your alarm may indicate a faulty alarm, you can refer to the Troubleshooting
section for a solution.
NOTE: WEEKLY TEST IS REQUIRED!
Pause function
The pause function allows the alarm circuit to temporarily not detect smoke for
approximately 10 minutes. The pause function should only be used to minimize
nuisance alarms when a known alarm condition, such as smoke from cooking, triggers
the alarm. Press the test button for at least 5 seconds (or until the unit sounds) to
activate the pause function and the alarm will go into pause mode for approximately 10
minutes. The smoke detector will automatically reset itself after approximately 10
minutes. If combustion particles are still present after this period, the smoke alarm will
sound again. The pause function can be repeated until the air is purified. Combustion
particles from cooking can set off the alarm if the alarm is located close to the cooking
area. Using an exhaust hood that ventilates to the outside (type without recirculation)
will help remove these combustible particles from the kitchen. Thus, the pause
function is extremely useful when the alarm is activated by cooking fumes.