Menu: Configuration
Programmable inputs explanatory
notes
0 Default, None
The "programmable input" function is
not used
1 Modem function active
when contact closed
The telephone remote switch (modem
function) is a central switching off or
transfer of the heating system to the
operating mode "Standby" or reduced t
2 Modem function active when
contact open
As 1, but the modem function is
activated when the phone switch
contact opens.
3 Warm air curtain function
The warm air curtain function causes
the boiler setpoint on parameter 2212
TKSmax to be set. In addition, a heat
demand for heating circuit 1 is set.
This function can be activated both in
summer and in winter..
The burner output modulation is
maintained
The drinking water priority is
maintained
The warm air curtain function is
active with a closed contact
A PWM pump control is not
affected
4 Preselected setpoint
(AGU 2511 and 2513 only)
The heat demand (temperature
requirement) is determined in this case
by an analogue signal. This can be
either a current signal (4...20 mA) or a
voltage signal (DC 0...10 V).
5
Preselected output
(AGU 2511 and 2513 only)
The relative boiler efficiency is
determined in this case by an
analogue signal.
6 Low loss header sensor input
This function allows boiler adjustment
to the flow temperature of the low loss
header. For this purpose, connect a
sensor to the clip-in function module
input, which must be placed on the
flow after the low loss header.
7 Check sign flue gas damper
When flue gas damper control is
active (programmable output), the
potable water flow switch is assigned
as input for flue gas damper feedback.
Alternatively, the feedback can also be
assigned to the programmable input.
8 Burner lock activated when
contact closed
The "burner lock" function is used for
the integration of alternative energy
sources (solid fuel, solar, etc.) needed
to inhibit the burner.
The "burner lock" function is used for
the integration of alternative energy
sources (solid fuel, solar, etc.) needed
to inhibit the burner.
9 Burner lock activated when
contact open
As 8 but the burner lock is activated
when the external contact opens.
10 Collector sensor (solar
Clip-In AGU 2530 only)
Using the collector sensor and an
additional storage tank sensor B3 or
B4, solar differential control can be
implemented.
11 Burner lock via temperature
sensor
The "burner lock via temperature
sensor" function is used for the
integration of alternative energy
sources (solid fuel, solar, etc.) needed
to inhibit the burner.
A temperature sensor detects the
temperature in the buffer storage
tank, and locks or releases the
burner as follows:
The burner is released when: Storage
tank sensor < boiler temperature
setpoint plus hysteresis
The burner is locked if: Storage
tank sensor < boiler temperature
setpoint minus hysteresis
40
40


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Elco Thision S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Elco Thision S in the language / languages: English as an attachment in your email.

The manual is 2,06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Elco Thision S

Elco Thision S User Manual - German - 20 pages

Elco Thision S User Manual - Dutch - 21 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info