Commissioning
Flue gas quantities and adjustment
Flue gas measurement and
adjustment
Combustion settings need to be set
with the boiler in commissioning mode
(via Flue Cleaner button (8)), setting
the boiler at Maximum load / Minimum
load and making adjustments at the
gas valves Max Output and MinM
output as required. (Ref P24 & 25)
When in the commissioning mode the
3-way valve (Combi Only) is diverted
to heating mode, the temperature limit
values of the boiler are disabled and
only the maximum safety temperature
remains activated (Q5°C)
Whilst in commissioning mode to put
Boiler at max output turn Service
Water adjustment (11) fully clockwise,
to put boiler into minm output trun
service water adjustment (11) fully
anti-clockwise
If an HG model boiler (heating
operation only) is used with underfloor
heating, interrupt the operation of the
boiler if the temperature exceeds
45°C. Resume operation after the
boiler has cooled.
Access for Analyser Readings
First unscrew the locking screw (1)
between the flue gas test points.
The test point plugs (E= emission, A=
intake air) can be removed with a 90°
anti-clockwise turn (bayonet closure).
Place the analyser Sensor into the
appropriate Test point for measurment.
Flue gas measurement is carried out in
heat mode. Analyser sensor to go in
approx 75mm for Emission checking.
On a Combi If system load is difficult to
achieve, for example during the summer,
the hot water circuit can also be used as
follows:
With the aid of a screwdriver
disconnect the fixing clamps, 3, of
the motor, 4, of the 3-way valve.
Steady the motor with your hand
meanwhile detach the motor, open
one or more hot water taps to let off
the heat generated during the
measurement of the heating
appliance and carry out the
measurement.
When measuring is completed, shut the
taps again, attach the motor, push it
down and replace the fixing clamps.
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Elco MHS - EURON 24 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Elco MHS - EURON 24 in the language / languages: English as an attachment in your email.

The manual is 2,98 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info