7) Signalling: H7 over heated fumes (turns off due to exceeding maximum smoke temperature).
Problem: Switches off because of overheated fumes.
Over heated fumes may depend on: type of pellets, anomalous fume extraction, blocked channel, incorrect
installation, gear motor drift, lack of air vents in the room.
8) Signalling: H8 H2O temp alarm (this occurs if the water temperature sensor reads a temperature
above 90°C)
Problem: Shuts down due to water temperature being higher than 90 °C.
An excessive temperature may occur because of the following:
• system too small: ask the DEALER to activate the ECO function
• blockage: clean the exchanger pipes, the combustion chamber and the smoke outlet.
9) Signalling: AL 09 (intervenes if the flow sensor detects insufficient combustion ).
Problem: Turns off for lack of depression
Air flow may be insufficient because the door is open, the door does not close properly (e.g. bad seal),there
is an air intake or smoke extraction problem, or the combustion chamber is clogged.
Actions: Check:
• door closure;
• combustion air intake duct (clean, paying attention to the flow sensor components);
• clean the flow sensor with dry air (like that used for PC keyboards);
• stove location: respect and check a minimum distance of 10 cm from the wall;
• combustion chamber position and cleanliness (clean regularly according to the type of pellet);
• smoke duct (clean);
• installation (if it does not comply with regulations or the smoke outlet has more than 3 bends);
If you suspect the sensor is malfunctioning, carry out cold tests. If the conditions are changed (for example
by opening the door) and the value does not change, there is a sensor problem (DEALER).
N.B.: The no depression alarm may also occur during ignition, since the flow sensor starts monitoring 90 secon
ds after the ignition cycle begins.
10) Signalling: “Bat. 1”
Problem: The boiler-stove does not stop but the error appears on the display.
Actions:• The buffer battery of the control board needs changing (DEALER).
11) Signalling: AL HC - HIGH CURRENT ALARM: Activated when anomalous, excessive current is
being absorbed by the gear motor.
Actions: Check functioning (CAT): gear motor - Electrical connections and electronic board .
12) Signalling: AL LC - LOW CURRENT ALARM: Activated when anomalous, insufficient current
absorption is detected on the gear motor.
Actions: Check functioning (CAT): gear motor - pressure switch - tank thermostat - electrical connections
and electronic board
NOTA
CHECK AIR ENTRY/NO DRAUGHT: these can occur only during the start-up phase at the end of the LEO-
NARDO system checks; though they do not cause the stove to shut down, we recommend contacting the Technical
Assistance Centre if the signal appears frequently.
N.B.:
The combustion chambers and smoke ducts connected to the solid-fuel appliances must be cleaned once a year
(check if your country has specific legislation covering this).
Failure to regularly check and clean increases the likelihood of a fire in the chimney pot.
IMPORTANT!!!
In the case of a fire in the boiler-stove, in the flue or in the chimney, proceed as follows:
- Disconnect the power supply
- Use a carbon dioxide (CO2) extinguisher
- Call the fire brigade
DO NOT ATTEMPT TO PUT THE FIRE OUT WITH WATER!
After the event, have the appliance checked by an authorised Service Centre and have an authorised technician
check the flue.
TROUBLESHOOTING
31


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Edilkamin Mito Idro at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Edilkamin Mito Idro in the language / languages: English as an attachment in your email.

The manual is 5.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Edilkamin Mito Idro

Edilkamin Mito Idro Usermanual and installation guide - German - 36 pages

Edilkamin Mito Idro Usermanual and installation guide - Dutch - 32 pages

Edilkamin Mito Idro Usermanual and installation guide - French, Italian - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info