ENGLISH
INSTALLATION
THE SMOKE CHANNELTHE SMOKE CHANNEL
• if in metal must have a CE marking (EN 1856-2) or
similar national law;
• cannot be in fl exible metal material
• to check the fl ow, a shutter is advised for draft over
25 Pa
THE CHIMNEY FLUE:THE CHIMNEY FLUE:
must have a draft capable of creating negative
pressure ideally around 12 Pa. Lower drafts can
cause leaking smoke if the door is open; higher
values tend to generate fast combustion by
reducing the yield
• must be correctly sized to meet smoke evacuation
(EN 13384-1)
• must preferably be insulated, in steel with a circular
inner section. If rectangular, the inner edges must
have a radius under 20 mm and a ratio between
between the inner dimensions <1.5
• normally have a minimum height of 3-4 metres
• maintain a constant section
• be waterproof and thermally insulated to guarantee
draft.
• preferably create a collection chamber for
unburned fuel and any condensate
• beat least category T400, with an adequate
resistance to soot fi reIf pre-existing, it must be
cleaned to avoid risk of fire.
THE CHIMNEY STACK THE CHIMNEY STACK
must be wind-proof
have an internal section equivalent to that of the
chimney flue and passage section outlet equal to
at least double the inner passage of the chimney
flue
for paired chimney flues (which should be at least
2 m apart) the chimney stack of the chimney flue
receiving the product discharge with solid fuel or
that of the highest fl oor must be at least 50 cm
taller
must go beyond the refl ux zone
must enable chimney maintenance
EXTERNAL AIR INTAKE (Figs. A-B)
The connection with the outside, made with a cross-
sectional area of at least 80/200 cm² (depending on
the model) is absolutely essential, as prescribed by
the standard governing installation requirements (UNI
10683).
It must, therefore, be provided.
It is made with a duct that must bring outside air
directly to the adjustment mechanism (Fig. B). The
regulation mechanism must be attached to the bottom
of Firebox®.
During installation, carefully seal the points where the
external air may leak.
The external air duct may come from behind, from
below, from the side, or consist of a fl exible hose
which runs directly from the outside to the mechanism
vent (Fig. B).
It is advisable to apply a protection grille on the outside
of the air-intake duct that does not, reduce the air-fl ow
capacity.
The external air must be drawn in at floor level.
If it is not possible to do as described above, place the
external air intake as near to Firebox® as possible.
12


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Edilkamin Firebox Deco at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Edilkamin Firebox Deco in the language / languages: English as an attachment in your email.

The manual is 1.13 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Edilkamin Firebox Deco

Edilkamin Firebox Deco Usermanual and installation guide - English - 80 pages

Edilkamin Firebox Deco User Manual - German - 28 pages

Edilkamin Firebox Deco Usermanual and installation guide - German, French, Italian, Portuguese, Spanish - 80 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info