ENGLISH
INSTALLATION
INSTALLER
FLUE
Further to the general prescriptions, the flue
must
must
only be used to discharge smoke
be correctly sized to satisfy the requirements of
smoke discharge (EN 13384-1)
must preferably be insulated, in steel with a circular
internal section. If rectangular, the corners must
have a radius of not less than 20 mm, with a ratio
of the internal dimensions of <1.5
must normally be at least 1.5 metres in vertical
length
must have a constant cross section
must be waterproof and thermally insulated to
ensure proper draught
preferably provide a collection chamber for
unburnt residues and condensates
if pre-existing, must be clean, to prevent fire
hazards
in general, we recommend fitting a tube inside the
existing masonry chimney if its diameter is greater
than 150 mm. This recommendation is purely
indicative; the installer must assess the actual
situation on-site after measuring the draught.
:
Besides the general prescriptions, the buried system
must:
operate in negative pressure;
• be inspectable;
comply with local regulations.
must:
• be windproof
have an internal cross-sectional area equivalent to
that of the flue and a smoke outlet at least double
that of the interior of the flue
extend beyond the back flow zone (in Italy, refer to
UNI 10683 point 6.5.8.)
allow for maintenance of the chimney
For dual flues (which should be spaced at least 2 m
apart), the chimney pot receiving the smoke from the
solid fuel appliance or the pot on the higher storey
must be at least 50 cm higher than the other
COMBUSTION AIR INTAKE
In general, we suggest two ways to ensure a proper
flow of combustion air. The air must be drawn from
outside*
Please remember to also ensure air exchange for
heating and glass cleaning air, etc.
Indirect air intake
The product draws air from outside through a hole in
the rear.
Install an air outlet at floor level with an effective sur-
face area (net of the screen or other protections) of at
least 80 cm2 (10 cm in diameter).
To prevent draughts, we recommend installing the
intake behind the product or behind a radiator.
Installing it in front of the appliance will create
unpleasant draughts.
Direct air intake **
Install an air intake of effective surface area (net of the
mesh or other protective equipment) equal to the cross
section of the air intake at the back of the product.
Connect the air intake to the appliance's air intake with
a pipe that may also be flexible. Increase the diameter
of the pipe if the pipe is not smooth: assess any load
loss.
We recommend not exceeding a 3 m length, taking
into account the flue draught. For each curve, up to a
maximum of two curves, the length should be reduced
by 1m. Assess whether or not to increase the diameter
of the pipe.
*The air may be drawn from an adjacent room only if:
the flow is taken from permanent and unobstructed
openings communicating with the outdoors;
the air pressure in the adjacent room is never
lower than that of the outdoor pressure;
the adjacent room is not a garage, subject to fire
hazard, a bathroom or a bedroom;
the adjacent room is not a shared room in the
condominium.
In Italy, UNI 10683 provides that ventilation is sufficient
even if a pressure difference between the outdoors
and indoors of no more than 4 PA is guaranteed (UNI
EN 13384-1). The installer who issues the declaration
of conformity is responsible for ensuring these
conditions.
**Direct connection to the air intake will not make the
product airtight. It is therefore necessary to additionally
ensure an air intake from within the room where the
product is installed (i.e. for cleaning the glass)
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Edilkamin Blade H 15 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Edilkamin Blade H 15 in the language / languages: English as an attachment in your email.

The manual is 4.2 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Edilkamin Blade H 15

Edilkamin Blade H 15 Usermanual and installation guide - German - 88 pages

Edilkamin Blade H 15 Usermanual and installation guide - French - 88 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info