PLEASE NOTE: FVI12 IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT
NOTICE. PLEASE VISIT WWW.ECCOTEMP.COM/SUPPORT FOR MORE INFORMATION.
English
Support: Eccotemp.com/help-desk Shop Online: Eccotemp.com/products Store Locator: Eccotemp.com/locator
In regards to the HOT WATER OUTLET:
• Connections between the water heater and point(s) of use
should be as short and direct as possible.
• DO NOT use lead or non-approved plastic pipe.
• To conserve energy and minimize heat loss, insulation of hot
water piping is recommended.
NOTICE: The pressure rate of hot water may vary when more
than two faucets (appliances, xtures, etc.) are being used
simultaneously.
NOTICE: The pipes MUST be completely drainable. If the hot
water faucets are located at a point higher than the water heater,
place a drain valve at the lowest point (see diagram to the left).
The Manual Gas
Appliance Shuto Valve
must be installed at
the gas connection of
the water heater at the
time of installation (see
diagram to the left).
The branch gas supply
line to the water heater
should be clean black
steel pipe or other
approved gas piping
material.
A ground joint union or
ANSI design certi ed
semi-rigid or exible
gas appliance connector
should be installed in the
gas line close to the water
heater.
The National Fuel Gas
Code (NFGC) mandates
a manual gas shut-o
valve: See (NFGC) for
complete instructions.
A sediment trap should be installed at
the bottom of the gas line.
The inlet gas pressure to the water
heater must not exceed 10.5“ w.c.
for natural or 14” w.c. for LP gas. For
purposes of input adjustment, the
minimum inlet gas pressure (with main
burner on) is shown
on the water heater rating plate. If
high or low gas pressures are present,
contact your gas supplier for correction
The water heater and its indivdual
shuto valve must be disconnected
from the gas supply piping system
during any pressure
testing of that system at test pressures
in excess of ½ psi (3.5 kPa). The water
heater must be isolated from the gas
supply
piping system by closing its individual
manual shuto valve during any
pressure testing of the gas supply
piping system at test pressures equal to
or less than ½ psi (3.5 kPa).
WARNING: Do not attempt to convert this water heater for use with a di erent type of gas other
than the type shown on the rating plate. Such conversion could result in hazardous operating
conditions. Please have a professional connect the gas pipe.
DO NOT use excessive force (over 31.5 ft lbs.) in tightening the pipe, particularly if pipe compound is
used, as the unit may be damaged.
Compound used on the threaded joints of the gas piping must be of the type resistant to the action of LP
gas. Use compound sparingly and use on male threads only.
Water Connections
Gas Supply
Installation
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Eccotemp FVI-12 series at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Eccotemp FVI-12 series in the language / languages: English as an attachment in your email.

The manual is 5.15 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info