10. SPECIAL PROGRAMMING
Important notes:
All parameters remain stored even if EasyAlar is switched off or without battery. Therefore
reprogramming is only essential if parameters have to be changed.
Programming mode can be locked to secure against unintended programming during operation (section 6.4.1).
If lock is activated, the announcement „programming inactive: PIN“ will be announced if function switch is
shifted to PROG.
Attention: Changing these parameters below does influence the operating mode. Therefore only necessary
parameters should be changed. Please test behaviour before putting the unit back into operation!
A programming error can be corrected by repeating the programming steps accordingly.
10.1 Factory settings (Default-Values)
EasyAlarm® can be reset to default values as follows:
OFF ON
PROG
Keep 3 and # pressed
simultaneously
OFF ON
PROG
Release keys
OFF ON
PROG
10.2 Alarm repetition
An alarm is triggered, as soon as the alarm criterion is fulfilled and the waiting period has expired. In some cases it might
be useful to repeat an alarm as long until an acknowledgement is received.
OFF ON
PROG
*. 9. 7. 1. 3 5 3 #. #. *. Value #.
OFF ON
PROG
Value Comment
0
EasyAlarm
®
calls the alarm numbers within the calling number sequence just once
1..9
EasyAlarm® starts calling the calling numbers within the calling number sequence until the alarm is
confirmed by DTMF 0 or until the programmed value is reached! (factory setting: Value=2)
10.3 Entry / Exit period
The appropriated register 4 8 an be read-out or modified as follows:
OFF ON
PROG
*. 9. 7. 1. 3 4 8 #. #. *. Value #.
OFF ON
PROG
Value Comment
0..255 Time in seconds (factory setting: Value=20)
10.4 Mains power loss timeout
The appropriated register 6 3 can be read-out or modified as follows:
OFF ON
PROG
*. 9. 7. 1. 3 6 3 #. #. *. Value #.
OFF ON
PROG
Value Comment
0 Mains power loss alarm disabled
1..255 Period for mains power loss, before a alarm is activated : in 10 minute steps ! (deviation: -10/+0min)
(factory setting: Value=2, i.e.. alarm is triggered if the mains voltage precipitates during 10..20min).
10.5 Signalling
10.5.1 .. through alarm unit
It is possible to signal the inactive waiting period with one beep every two seconds. Proceed as follows:
OFF ON
PROG
*. 9. 7. 1. 3 0 5 #. #. *. Value #.
OFF ON
PROG
Signalling..Value
Mains loss at power-on Selected mode after power-on Exit Beep every 2 sec. Entry: 2 Beep
0
1
2
3
4
Value
Value
Value
Value
Prog. 2
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for EasyAlarm CONTROL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of EasyAlarm CONTROL in the language / languages: English as an attachment in your email.

The manual is 0,98 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of EasyAlarm CONTROL

EasyAlarm CONTROL User Manual - German - 32 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info