English LI 20TES - LI 28TES
7.3 Heating System Connection
The heating system connections on the heat pump have a 1 ¼"
external thread. Use a spanner to firmly grip the transitions
when connecting the heat pump.
Before connecting the heating water system to the heat pump,
the heating system must be flushed to remove any impurities,
residue from sealants, etc. Any accumulation of deposits in the
liquifier could cause the heat pump to completely break down.
For systems in which the heating water flow can be shut off via
the radiator or thermostat valves, an overflow valve must be in-
stalled in a heating bypass behind the heat pump by the cus-
tomer. This ensures a minimum heating water flow rate through
the heat pump and helps to avoid faults.
Once the heating system has been installed, it must be filled,
de-aerated and pressure-tested.
Consideration must be given to the following when filling the
system:
Untreated filling water and make-up water must be of
drinking water quality (colourless, clear, free from sedi-
ments)
Filling water and make-up water must be pre-filtered (pore
size max. 5 µm).
Scale formation in domestic hot water heating systems cannot
be avoided, but in systems with flow temperatures below 60 °C,
the problem can be disregarded. With high-temperature heat
pumps and in particular with bivalent systems in the higher per-
formance range (heat pump + boiler combination), flow tem-
peratures of 60 °C and more can be achieved. The following
standard values should therefore be adhered to with regard to
the filling and make-up water according to VDI 2035, sheet 1:
The total hardness values can be found in the table.
Fig. 7.1:Guideline values for filling and make-up water in accordance with
VDI 2035
For systems with an above-average specific system volume of
50 l/kW, VDI 2035 recommends using fully demineralized
water and a pH stabiliser to minimize the risk of corrosion in the
heat pump and the heating system.
ATTENTION!
!!
With fully demineralized water, it is important to ensure that
the minimum permissible pH value of 7.5 (minimum
permissible value for copper) is complied with. Failure to
comply with this value can result in the heat pump being
destroyed.
Minimum heating water flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished, for example, by installing either a
dual differential pressureless manifold or an overflow valve. The
procedure for setting an overflow valve is described in the
chapter "Start-up". When the minimum heating water flow rate
is undershot, the plate heat exchanger in the refrigeration cir-
cuit can freeze, which can lead to total loss of the heat pump.
The nominal flow rate is specified depending on the max. flow
temperature in the device information and must be taken into
account during planning. With design temperatures below 30 C
in the flow, the design must be based on the max. volume flow
with 5 K spread for A7/W35.
The specified nominal flow rate (See “Device Information” on
page 13.) must be guaranteed in every operating status. An in-
stalled flow rate switch is used only for switching off the heat
pump in the event of an unusual and abrupt drop in the heating
water flow rate and not to monitor and safeguard the nominal
flow rate.
NOTE
º
The use of an overflow valve is only recommended for panel
heating and a max. heating water flow of 1.3 m³/h. System
faults may result if this is not observed.
Antifreeze
Heat pump systems, which cannot be guaranteed to be frost-
free, should be equipped with a drainage option (see Fig.).The
antifreeze function of the heat pump manager is active when-
ever the heat pump manager and the heat circulating pump are
ready for operation. If the heat pump is taken out of service or
in the event of a power failure, the system has to be drained.
The heating circuit should be operated with a suitable anti-
freeze if heat pump systems are implemented in buildings
where a power failure can not be detected (holiday home).
7.4 Temperature sensor
The following temperature sensors are already installed or must
be installed additionally:
External temperature sensor (R1) supplied (NTC-2)
Return temperature sensor (R2) installed (NTC-10)
Flow temperature sensor (R9) installed (NTC-10)
Total heat
output in kW
Total alkaline earths
in mol/m³ and/or
mmol/l
Specific system volume
(VDI 2035) in l/kW
< 20 20 < 50 50
Total hardness in °dH
< 50 2.0 16.8 11.2
< 0.111
50 - 200 2.0 11.2 8.4
200 - 600 1.5 8.4 < 0.111
> 600 < 0.02 < 0.111
1. This value lies outside the permissible value for heat exchangers in heat
pumps.
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex LI 20TES at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex LI 20TES in the language / languages: English, German, French as an attachment in your email.

The manual is 2.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info