LAK 3IMR - LAK 14ITR English
7 Connecting the pipework
and cables to the outdoor
unit
This chapter describes the refrigerant pipe connections and the
electrical cable connections on the outdoor unit.
7.1 Refrigerant pipes
CAUTION!
!
!
Work on the system must only be performed by authorised
and qualified after-sales service technicians!
Certain requirements with regard to pipe length and rise must
be complied with when installing refrigerant pipes. Once all re-
quirements have been fulfilled, certain preparations must be
made.
Once these are complete, the connecting pipe from the out-
door unit to the indoor unit can be connected.
7.1.1 Requirements for pipe length
and rise
The standard pipe length is 7.5 m. Up to a length of 15 m, no
additional refrigerant filling is required. For pipe lengths over 15
m, the system must be filled with additional refrigerant in ac-
cordance with the table.
*Example: When installing the 14 kW model at a distance of
50 m, 2100 g refrigerant must be added according to the fol-
lowing calculation: (50-15) x 60 g = 2100 g
NOTE
º
ºººº
If the indoor unit is mounted 4 or more metres higher than the
outdoor unit, a cooling technology specialist must perform a
separate check to ensure that the devices for conveying the
oil up and down the pipes have been installed correctly in the
hot gas pipe.
NOTE
º
ºººº
The rated output of the device corresponds to the standard
pipe length and the maximum possible length.
CAUTION!
!
!
Incorrect filling with refrigerant could lead to faults during
operation.
1) Production operation (see model name label)
2) Installation operation (where possible, attach alongside the
maintenance connections for adding or removing refriger-
ant)
3) Total filling (1, + 2,)
7.1.2 Preparation for pipework
The preparation of the pipework takes place in five steps. One
main cause of refrigerant leaks is incorrect flanging. Flanging
must be carried out carefully and according to the following
steps.
Step 1: Cutting pipes and cables
Use the installation kit for pipework or the pipes purchased
from your local dealer.
Measure the distance between the indoor and outdoor
unit.
Cut the pipes slightly longer than the measured distance.
Step 2: Removing burrs
Remove all burrs from the interface of the pipework.
Hold the pipe end downwards so that no burrs can fall into
the pipe.
Step 3: Inserting screw nuts
Remove the screw nuts on the indoor and outdoor unit.
Insert the screw nuts into the deburred pipe.
No nuts can be inserted into the pipe after flanging.
Model
Pipe size (mm)
(diameter: ) Length A (m) Rise B (m) *additional
refrigerant
(g/m)
Gas Liquid Normal Min. Max. Normal Max.
3 kW 12
(1/2“)
6
(1/4“) 7.5 2 25 0 15 15
6 kW
9 kW
15.88
(5/8")
9.52
(3/8") 7.5 3 50 0 30 30
14 kW 15.88
(5/8")
9.52
(3/8") 7.5 3 50 0 30 60
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
Copper pipe
90qTilted Uneven Raw
Pipe
Reamer
Hold facing
downwards
Screw nut
Copper pipe
35


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex LAK 14IMR at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex LAK 14IMR in the language / languages: English, German, French as an attachment in your email.

The manual is 7.79 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info