LA 33TPR English
Minimum heating water flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished, for example, by installing a dual dif-
ferential pressureless manifold.
CAUTION!
!
!
When the minimum heating water flow rate is undershot, the
plate heat exchanger in the refrigeration circuit can freeze,
which can lead to total loss of the heat pump.
The nominal flow rate is specified depending on the max. flow
temperature in the device information and must be taken into
account during planning. With design temperatures below
30°C in the flow, the design must be based on the max. volume
flow with 5 K spread for A7/W35.
The specified nominal flow rate (Cap. 13 on page 18) must be
assured in all operating states. An installed flow rate sensor is
used only for switching off the heat pump in the event of an un-
usual and abrupt drop in the heating water flow rate and not to
monitor and safeguard the nominal flow rate.
Frost protection
On heat pump systems where protection from frost cannot be
guaranteed, there must be an option for draining the system
(see figure). The frost protection function of the heat pump
manager is active whenever the heat pump manager and the
heat circulating pump are ready for operation. When decom-
missioning the heat pump, or in the event of a power failure, the
system must be drained through the indicated points (see illus-
tration); it may be necessary to purge the system with com-
pressed air. The heating circuit should be operated with a suita-
ble frost protection if heat pump systems are implemented in
buildings where a power failure cannot be detected (holiday
home).
7.4 Temperature sensor
The following temperature sensors are already installed or must
be installed additionally:
Outside temperature (R1) supplied (NTC-2)
Return temperature, secondary circuit (R2) installed
(NTC-10)
Flow temperature in secondary circuit (PT 1000) integrated
in flow rate sensor (R3.1)
7.4.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump
manager (controller -N1) must correspond to the sensor char-
acteristic curve illustrated in Fig. 7.2 on page 13. The only ex-
ception is the outside temperature sensor included in the scope
of supply of the heat pump (see Fig. 7.3 on page 13)
Fig. 7.2:Sensor characteristic curve NTC-10
Fig. 7.3:Sensor characteristic curve NTC-2 according to DIN 50350 Out-
side temperature sensor
2
1
3
Temperature in °C -20 -15 -10 -5 0 5 10
NTC-2 in k14.6 11.4 8.9 7.1 5.6 4.5 3.7
NTC-10 in k67.7 53.4 42.3 33.9 27.3 22.1 18.0
15 20 25 30 35 40 45 50 55 60
2.9 2.4 2.0 1.7 1.4 1.1 1.0 0.8 0.7 0.6
14.9 12.1 10.0 8.4 7.0 5.9 5.0 4.2 3.6 3.1
0
10
20
30
40
50
60
70
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
0
2
4
6
8
10
12
14
16
18
20
-20-15-10-5 0 5 1015202530354045505560
External temperature in [°C]
Resistance value in [kOhm]
37


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex LA 33TPR at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex LA 33TPR in the language / languages: English, German, French as an attachment in your email.

The manual is 3.6 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info