EN-10 452166.66.14 · FD 0008 www.glendimplex.de
English LA 33TPR
The heat pump is not an ignition source. When installing several
heat pumps, the safety zone or must be established
around the entire group of heat pumps. The maintenance dis-
tances between the individual heat pumps must be adhered
to.
CAUTION!
!
!
The heat pump must be installed in such a way that any
leaking propane cannot enter the building or pose a danger to
people in any other way.
If other devices are installed within the safety zone or ,
their components within the safety zone must not constitute a
source of ignition.
If the implementation of the installation conditions described
above is not possible, replacement measures can be applied.
The operator must agree these replacement measures with the
local authorities and/or independent test centres (e.g. the use
of propane detectors which disconnect all sources of ignition in
the safety zone from the power supply in the event of a leak-
age).
NOTE
º
ºººº
The heat pump’s safety zone may only be accessed by
authorised and instructed personnel.
A sign must be mounted at the entrance to the installation area
that points out the hazards, provides instructions on how to act
and states that the area may only be entered by instructed per-
sonnel.
CAUTION!
!
!
Do not restrict or block the area around the intake or the air
outlet area.
NOTE
ººººº
Observe country-specific building regulations!
CAUTION!
!
!
Installation in a hollow or in an inner courtyard is not
permitted because cooled air collects at ground level and is
drawn in again by the heat pump during extended periods of
operation.
CAUTION!
!!
The heat pump, especially its refrigeration circuit, must be
protected against damage during installation and other
construction methods.
NOTE
º
ºººº
The physical impacts must be observed for installation close
to walls. No windows or doors should be present in the area
surrounding the air outlet of the fan.
NOTE
ººººº
In cases of installation close to walls, there may be more
contamination in the intake and air outlet area due to the air
flow. The colder outside air outlet should discharge in such a
way as to not increase the heat losses in heated neighbouring
rooms.
6.4 Condensate pipe for heat
pumps with flammable
refrigerant
Frost-free condensate discharge must be guaranteed. To en-
sure proper drainage, the heat pump must stand horizontally.
NOTE
º
ºººº
The frost line may vary according to the climatic region.
The regulations of the countries in question must be
observed.
Version 1
The condensate, which accumulates during operation, must be
drained vertically into a base filled with gravel. A daily seepage
capacity of at least 1.5 litres per kW heat output of the heat
pump shall be provided and the diameter of the condensate
water pipe should be at least 50 mm.
Fig. 6.3:Condensate drain in gravel
NOTE
º
ºººº
The condensate water pipe must be installed vertically to
prevent it from freezing in winter.
Version 2
The condensate is channelled into a sewer, rainwater or drain-
age channel via a condensate pipe in the ground. The conden-
sate pipe contains a siphon below the frost line . The water
level in the siphon prevents the refrigerant from getting into the
channel if there is a leakage. Pumping systems are impermissi-
ble!
The siphon must have a minimum sealing liquid level of
300 mm. The condensate drain must be checked during main-
tenance to ensure that it is working correctly and has no leaks.
Fig. 6.4:Condensate pipe in channel over siphon
4
4
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex LA 33TPR at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex LA 33TPR in the language / languages: English, German, French as an attachment in your email.

The manual is 3.6 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info