www.glendimplex.de 452166.66.14 · FD 0008 EN-3
LA 33TPR English
2 Intended use of the heat
pump
2.1 Area of application
The heat pump is suitable for mono energy and bivalent opera-
tion in outside air temperatures to -22°C.
Proper defrosting of the evaporator is guaranteed by maintain-
ing a heating water return temperature of more than 22°C dur-
ing continuous operation. The maximum water outlet tempera-
ture must not exceed 64°C and must be secured on the system
side so that, if the temperature is exceeded, all additional heat
sources are switched off safely.
The heat pump is not designed for the increased heat con-
sumption required when a building is being dried out. For this
reason, the additional heat consumption should be met using
special devices provided by the customer. For drying out a
building in autumn or winter, it is advisable to install a second
heat generator (e.g. an electric heating element available as an
accessory).
In cooling operation, the heat pump is suitable for air tempera-
tures ranging from +10°C to +45°C.
It can be used for silent and dynamic cooling. The minimum
cooling water outlet temperature is +10°C.
NOTE
º
ºººº
The device is not suitable for operation with a frequency
converter.
2.2 Operating principle
Heating with the heat source air
Surrounding air is drawn in by the fan and fed through the evap-
orator (heat exchanger). The evaporator cools the air, i.e. ex-
tracts heat from it. This extracted heat is then transferred to the
working medium (refrigerant) in the evaporator.
The heat is "pumped" to a higher temperature level by increas-
ing its pressure with the aid of the electrically driven compres-
sors. It is then transferred to the heating water via the liquefier
(heat exchanger).
Electrical energy is used to raise the temperature level of the
heat from the environment. Since the energy extracted from
the air is transferred to the heating water, this type of device is
referred to as an air-to-water heat pump.
The air-to-water heat pump consists of the main components
evaporator, fan and expansion valve, as well as the low-noise
compressors, the liquefier and the electrical control system.
At low ambient temperatures, humidity accumulates on the
evaporator in the form of frost, reducing the transfer of heat.
Uneven accumulation during this process does not indicate a
fault. The evaporator is defrosted automatically by the heat
pump as required. Under certain atmospheric conditions,
steam may be emitted from the air outlet.
Cooling
The functions of the evaporator and the liquefier are reversed in
the "Cooling" operating mode.
The heating water transfers its heat to the refrigerant via the liq-
uefier, which is now functioning as an evaporator. The refriger-
ant is brought to a higher temperature level using the compres-
sor. Heat is transferred to the surrounding air via the liquefier
(which, in heating operation, functions as an evaporator).
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex LA 33TPR at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex LA 33TPR in the language / languages: English, German, French as an attachment in your email.

The manual is 3.6 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info