5.9.2.2 - fan mode
Enter
Select the mode
fan mode
fan mode
2
5.9.2.3 - T°C. MINI Minimum temperature
The electrical back-up can be activated at the same time as the
heat pump to prevent the water temperature from going below
a minimum comfort level of 38oC. The electrical back-up will start
up and raise the water temperature to 43oC, and then it will switch
o and the heat pump will complete the heating cycle.
• Press to return to the main menu.
This function is deactivated by default.
5.9.2.4 - Load shedding -Level authorised
during peak hours
5.9.2.5 - max time Max heating time
Enter
Select mode
T°C. MINI
no
T°C. MINI
yes
Enter
Select the mode
shedding
1
shedding
0
When load shedding is activated you can choose to prevent
certain elements from running (Electrical resistance and
compressor).
• Press to return to the main menu.
If load shedding is switched on:
Mode 0 = No element is allowed to operate
Mode 1 = Only the heat pump is allowed to operate
Mode 2 = The heat pump and back-up are allowed to operate
(neutralising the «peak hours» function)
If the PV function is activated, load shedding cannot be done
through the peak/o-peak hours dry contact. In this case the
timer must be programmed (see § «Programming»).
It is possible to select the length of the desired heating time. The
heat pump water heater can automatically use the electrical back-
up at the same time as the heat pump to speed up the heating
time of the tank.
If you choose MAX time = AUTO, the heating time is limited to a
maximum of 5h during o-peak hours.
• In case of load shedding the «T°C mini» function is not activated.
Factory setting= 1
Mode 1 = Standard mode, automatic ventilation
Mode 2 = Forced ventilation, max speed
Mode 3* = Ventilation activated during water heating periods
and ventilation regulated by an external control
(such as a moisture sensor)
The external control should be connected to connector 2 on the
electronics board in the heat pump water heater. (See appendix
for electrical diagram)
*If PV mode is activated, controlled ventilation (fan moDE 3) is not
available.
• Press to return to the main menu.
Enter
Select time period
between 1 and 24 hours
max time
no
max time
3h
This function is deactivated by default.
• Press to return to the main menu.
5.9.3 -Locking the keyboard
Enter
Select locking level
locking
locking
no
Permanent and automatic locking
The «locking» menu enables you to create three possible levels of
locking for accessing the menus.
In the «Installer» menu turn the dial to «locking.».
NO = Locking is not activated, but manual
locking is possible by pressing
for 3 seconds.
• If a cycle is interrupted by a period where the back-up is not
allowed to run (electricity provider signal or programmed time
slots) it will relaunch during the next authorised period.
•No anti-legionellosis cycle except when returning from holidays
and after a frost protection period of more than 3 days.
•During the anti-legionellosis cycle the temperature is raised
between 55°C and 70°C.
- INSTALLER HEAT PUMP WATER HEATER 200 -270L AIR D/2 - MANUAL-
14
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Dimplex Edel 200 AIR D-2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Dimplex Edel 200 AIR D-2 in the language / languages: English as an attachment in your email.

The manual is 2.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Dimplex Edel 200 AIR D-2

Dimplex Edel 200 AIR D-2 User Manual - Dutch - 48 pages

Dimplex Edel 200 AIR D-2 Installation Guide - Dutch - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info