608109
13
Zoom out
Zoom in
Previous page
1/24
Next page
13
16/07/2015 - 300028005-001-04 TRIO DT 250 - TRIO DT 350
Measured value TC - Collector temperature
The value TC shows the temperature in °C given by the collector
sensor in real time.
Measured value TS - DHW sensor temperature
The value TS shows the temperature in °C given by the tank sensor
in real time
Measured value kWh - Amount of heat
The value kWh shows in kWh the total amount of heat produced by
the installation since the regulator was put into service.
The quantity of heat (kWh value) can only be used for checks
carried out for personal reasons.
Measured value tc - Self-calibration time
The value tc shows the self-calibration phase time remaining in
seconds. During the self-calibration phase, the pump operates at full
speed (100 %); its speed is only controlled after the self-calibration
phase.
Measured value TM - Additional temperature
An optional additional temperature sensor can be connected to
terminals 7 and 8. For example: Temperature in the top of the
calorifier.
Adjustment parameter ANL -Type of installation
The adjustment parameter ANL is used to select the following
installation configurations:
ANL 1 = Installation 1:
- Preparation of domestic hot water using a DIETRISOL TRIO
calorifier.
- Preparation of domestic hot water using a tank with 2 exchangers
connected to the solar circuit.
ANL 2 = Installation 2:
Solar installation for the preparation of domestic hot water with a DC
mixed calorifier and for heating back-up with temperature control on
the heating return circuit. The temperature control on the heating
return circuit prevents the boiler having to maintain the temperature
of the back-up volume in the calorifier in the event of prolonged
absence of sunshine.
Adjustment parameter DO - Temperature
difference enabling the passage of the heating
return via the solar tank
Adjustment range: 0.5 ... 19.5 K
Factory setting: 6 K
The parameter DO is used to set the temperature difference above
which heating return is directed via the 3-way valve to the solar tank.
Heating return thus passes via the solar tank if the solar tank
temperature is higher by at least 6°C than the heating return
temperature.
If the parameter ANL is set to 1 (installation 1), the parameter
DO is deactivated
Adjustment parameter DF - Temperature
difference enabling heating return directly to the
boiler
Adjustment range: 0.4 ... 19.5 K
Factory setting: 4 K
The parameter DF is used to set the temperature difference below
which heating return is directed from the 3-way valve directly to the
boiler. The solar energy stored in the solar tank is insufficient to
reheat the heating return. Heating return is thus directed directly to
the boiler if the solar tank temperature is lower by at least 4°C than
the heating return temperature.
If the parameter ANL is set to 1 (installation 1), the parameter
DF is deactivated
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for De Dietrich DIETRISOL TRIO DT 250 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of De Dietrich DIETRISOL TRIO DT 250 in the language / languages: English as an attachment in your email.

The manual is 1,49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info