TDMA CONTROL 601/701:
59
Published 07/2007
5.7 Electrical Connection
The CONTROL 701 must be connected to an external
mains electricity supply at 230 V ± 10 % (50-60 Hz). The
connection is made at the L/ N/ PE clamps (see connec-
tion circuit board diagram 2).
Outputs 1 – 14 are each 230 Volt outputs. Their users are
connected to clamps A1 to A14.
Outputs 15 and 16 are voltage free outputs. Output 15
should be connected to clamps U1A/ U1M/ U1B. U2A/
U2M / U2B are where the user of output 16 is connected.
When outputs 15 an 16 are not activated, contact M-A is
open and contact M-B is closed.
Should the voltage free output have a 230 V output, the
operating voltage for outputs A15 and A16 can be a-
chieved using a bridge from clamp LS to U1M or U2M.
If a modulated input signal boiler is connected, it should
be connected to clamps U (0 – 10V) and GND.
The temperature sensors are connected to clamps F1 to
F16. The polarity of the temperature sensor connections is
open to choice. To prevent damage to the collector sensor
from being struck by lightening, a high voltage protection
for the installation is recommended (Art.-N
o
. RE500).
Clamps D1 and D6 are where the digital inputs are to be
connected.
ADVICE ON ELECTRICAL INSTALLATION GUIDELINES:
The relevant electrical installation guidelines must be
followed. The temperature sensor cables carry a low
voltage and must not be laid in the same channels as
other cables carrying voltages higher than 50V.
NOTE ON CONNECTION LAYING:
The connections should be made following the Regula-
tor Connection Information given in paragraph 4.
ADVICE ON SENSOR FAULTS:
If there is a faulty sensor and the flashing display pre-
vents setting the regulator, the sensor fault notification
can be overridden for 5 minutes by pressing "+" and "-
".
ADVICE ON POSITIONING THE COLLECTOR SENSOR:
The collector sensor should be fitted to the furthest pos-
sible absorber plate, so that it is also exposed to the in-
solation. Incorrect positioning of the collector sensor
can lead to inexact temperature measuring in the col-
lector and to a malfunction of the regulator.
If an immersion casing is used a good contact between
the sensor and the casing must be ensured. In must
cases using heat conducting paste is recommended. On
no account should the collector sensor be fitted outside
the collector.
Example of maximum cable lengths:
Sensor/Interface
Cable
Length up to
PT 1000
2 X 0.75 mm
25 m
PC-Interface
With standard
serial cable
50 m
Fuses
L1 Phase (black)
PE earth wire (yellow-green)
Solar pump
N Nullleiter (blue)
Output 1…14 (230V)
Digital inputs
3 and 4
Temperature sensor F1…F8
Module 1
Insolation sensor
Remote
Control
Module.
Output
Output 16
2,5AT
Output 1-4/LS
Temperature sensor F9…F16
Digital /inputs
5 and 6
Module 2
Output 15
2,5AT
Output 5-9/LS
2,5AT Output 10-
1-4/LS
Digital inputs
1 and 2
Diagram 2: Connection circuit board of the CONTROL 701 with solar pump connection example
CONTROL 701
59


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Consolar Control 601 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Consolar Control 601 in the language / languages: English as an attachment in your email.

The manual is 5,12 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info