Power and Protection Indicators
The power and protection indicators include a green
light, a red light and an alarm.
Green Light
Power on The green light should remain on steady.
Red Light and/or Alarm
Current overload The red light will blink continuously,
then the inverter will shutdown. The inverter will continue
to check for appropriate current levels while trying to
restart the load.
DC input voltage overload The red light will turn on and
the inverter will shutdown. The inverter will continue to
check for appropriate voltage levels while trying to restart
the load.
DC input voltage shortage As a warning that the voltage
is getting low, the internal alarm will sound. When the
voltage is too low, the inverter will shutdown and the red
light will turn on. The inverter will continue to check for
appropriate voltage levels while trying to restart the load.
Temperature overload The red light will blink, then the
inverter will shutdown. The inverter will continue to check
for appropriate temperature levels while trying to restart
the load.
NOTE A momentary sound of the internal alarm
and/or flash of the red light is normal at start up.
Power and Protection
Indicators
Operation
Operating Limits
Operation
Operating Limits
Power Output
The inverter can deliver 400 watts for about 60 minutes.
The inverter must cool for 15 minutes before it can
resume operation at 400 watts. Note: The wattage
rating applies to resistive loads.
The inverter will operate most AC loads within its power
rating. Some induction motors used in freezers, pumps,
and other motor-operated equipment require very high
surge currents to start. The inverter may not be able
to start some of these motors even though their rated
current draw is within the inverter’s limits. The inverter
will normally start single phase induction motors rated
at one-half HP or less.
Input Voltage
The inverter will operate from input voltage ranging
from 10 volts to 15 volts. Optimum performance will
occur when the voltage is between 12 volts and 14 volts.
If the voltage drops below 10.5V+/-0.3V, an audible low
battery warning will sound. The inverter will shut down if
the input voltage drops below 9.5V+/-0.3V. This protects
the battery from being over-discharged. It will restart when
the input voltage exceeds 12V+/-0.3V.
The inverter will also shut down if the input voltage
exceeds 15.75V+/-0.75V. This protects the inverter
against excessive input voltage. Although the inverter
has protection against over-voltage, it may still be
damaged if the input voltage were to exceed 16 volts.
Nothing Comes Close to a Cobra
®
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Cobra CPI 480 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Cobra CPI 480 in the language / languages: English as an attachment in your email.

The manual is 0,44 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info