6720818454 (2016/02) US SSB
24 | Installation
Remodeling areas;
Garages with workshops.
4.7.1 General venting and combustion air piping system
The SSB boilers require an approved vent system-designed for positive
pressure.
Vent connectors serving appliances vented by natural draft shall not be
connected to any portion of mechanical draft systems operating under
positive pressure.
Ensure that the ue pipes and seals are not damaged.
Use only primer and glue compounds approved for use with the vent
material used.
Never install a barometric or a thermally controlled vent damper with this boiler.
Do not route the ue system piping through or inside another duct that is
used for exhausting air or other ue gases.
The condensate trap must be primed at all times. Failure to do so may
allow combustion gases to escape into boiler room.
The unit is to be used for either direct vent installation or for installation
using room air for combustion. When room air is used, it is necessary to
provide an adequate opening for the fresh air intake.
You must use any of the vent/air piping methods shown in this manual.
Be sure to locate the unit such that the vent and combustion air piping
can be routed through the building and properly terminated.
The boiler / vent installation must be in accordance with Venting
of Appliances, of the latest edition of the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 or section, Venting Systems and Air Supply
for Appliances, of the CAN/CSA B149.1, Natural Gas and Propane
Installation code or applicable provisions of the local, state and federal
building codes.
All vent pipes must be installed according to the vent manufacturer’s
instructions.
The exhaust vent and the combustion air inlet lines must be supported to
prevent sagging per the vent manufacturer’s instructions.
Do not mix components from different systems. The vent system could
fail, causing leakage of ue products into the living space. Use only
approved materials.
Use of cellular core PVC and CPVC for venting system is not allowed.
WARNING: Improper venting due to failure to comply with
the warnings above can result in excessive levels of carbon
monoxide!
The exhaust pipe must be pitched a minimum of a 1/4 inch per foot back
to the boiler (to allow drainage of condensate).
The vent system shall be installed so as to prevent the accumulation of
condensate.
Consult local and state codes pertaining to special building code and re
department requirements. Adhere to national code requirements.
Observe the listed maximum lengths of vent system, which are boiler
model dependent
To avoid moisture and frost build-up and to maintain clearances to openings
on adjacent structures, 45 ° and 90 ° elbows or tees may be attached to
the end of the vent termination pipe to direct exhaust plumes away from
the adjacent structure. The total allowable vent length, maximum number of
elbows and distance to air intake restrictions must be adhered to.
Due to the high efciency of the unit it may discharge what looks like
white smoke especially when the outside air temperature is cold. This
is due to the presence of water vapor, normally present in the exhaust
gases.
The following gure shows the acceptable piping installation for venting
and combustion air.
Fig. 25
Two pipes side wall
(Direct venting)
Two pipes vertical
(Direct venting)
Air intake side wall,
vent vertical
(Direct venting)
Air intake vertical,
vent side wall
(Direct venting)
Concentring
vertical pipe
(Direct venting)
Concentring side
wall pipe
(Direct venting)
One pipe venting
side wall (or vertical)
(Not direct venting)
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus SSB512 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus SSB512 in the language / languages: English as an attachment in your email.

The manual is 9,92 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus SSB512

Buderus SSB512 Installation Guide - French - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info