Commissioning and shutting down
MCM10
67
4 Commissioning and shutting down
4.1 Configuration
With this configuration, the control characteristics of the
MCM10 master module are adapted to the specific
heating system.
The MCM10 module is configured automatically:
when commissioning a MCM10 module,
during a restart following a reset of the configuration
(Æ chapter 4.3).
Wait 5 minutes until the configuration has been
completed. During configuration, the LEDs associated
with the connected boilers and possibly the LED to
indicate BUS communication (Æ tab. 10, page 68) flash.
Configuration is completed and saved to the MCM10
when no more LEDs are flashing.
Any configuration saved remains in the memory, even in
case of power failure.
If, after configuration, a boiler (or a MCM10 module) is
temporarily shut down during active operation (e.g. for
maintenance), the LED assigned to that boiler or the
LED to indicate BUS communication begins to flash.
Following a restart, the boiler (or MCM10 module) will be
recognised, and the associated LED stops flashing.
4.2 Commissioning
B Ensure the correct connection of all heating system
components.
B Provide the power supply (230 V AC) for all
components of the heating system, except for
MCM10 modules.
B Start all boilers (switch ON).
B Provide the power supply via the mains plug of the
(first) MCM10 module.
Configuration commences. Wait 5 minutes until the
configuration has been completed.
B Make the necessary adjustments on the individual BUS
subscribers in accordance with their installation
instructions.
4.3 Configuration reset
During the next start, the current system configuration is
saved to the MCM10 module.
B Interrupt the power supply (230 V AC) to all
components in the heating system and all MCM10
modules.
B Open the MCM10 master module casing (Æ fig. 7,
page 64).
B Remove jumper (Æ fig. 4, page 63).
B Ensure the correct connection of all heating system
components.
B Provide power (230 V AC) to all components of the
heating system, except for MCM10 modules.
B Start all boilers (switch ON).
B Provide the power supply to the MCM10 master
module.
B To prevent fault functions: with system versions 2 or 3,
ensure that the jumper is inserted at the correct
position.
B Refit jumper (Æ fig. 4, page 63).
Configuration starts. Wait 5 minutes until the
configuration has been completed.
B Close MCM10 module casing.
4.4 Shutting down
B Interrupt the power supply to all MCM10 modules and
all boilers.
Troubleshooting in case of faults becomes
more difficult if the saved configuration does
not match the actual configuration of the
heating system.
B Implement a configuration reset after any
intended/remaining modification of the
system configuration (Æ chapter 4.3), to
enable the new system configuration to be
saved in the MCM10 master module.
The cascade configuration is set at the
MCM10 module during commissioning or
after a reset (Æ chapter 4.1).
B Monitor the LEDs during configuration to
detect lead/cable breaks or wiring faults.
The heating system configuration is saved in
the MCM10 master module. Resetting the
MCM10 master module deletes the
configuration of all MCM10 modules.
67


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus MCM10 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus MCM10 in the language / languages: English as an attachment in your email.

The manual is 3,04 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info