18 | Commissioning
MC 4006 720 816 739 (2015/05)
4.5 Cascade settingsmenu
When a cascade module is installed, the menu Service menu > Cascade
settings is displayed on the user interface (not available for all user
interfaces). When this menu is not available in the installed user
interface, the cascade module uses default settings. These settings can
be changed with an appropriate user interface even when the user
interface is only temporarily connected.
4.6 Diagnosismenu
The menus depend on the installed user interface and the installed
system.
Monitored values
If a MC 400 module is installed, the Monitored values > Cascade menu
is displayed.
This menu allows you to call up information on the current status of the
system and the individual devices in the cascade. For example, you can
display the level of the system's flow and return temperature, or the
current appliance output.
If a MC 400 module is installed, the menu Monitored values > System
information > Cascade is displayed.
This menu allows you to call up information on the MC 400 module
(cascade module type, cascade module software version) and the
individual devices in the cascade (such as control device 1 type,
control unit 1 software version).
The information and values that are provided depend on the system that
has been installed. Observe the documents for the heat source, user
interface, additional modules and other system components.
The default settings are shown in bold in the adjustment
ranges.
Menu item Adjustment range Function description
Offset header sensor – 20 ... 0 ... 20 K The flow temperature demanded by the control is changed by this value.
Set temp. cascade max 30 ... 90 °C Maximum flow temperature of the cascade at the low loss header.
Casc. pump overrun time 0 ... 3 ... 15 min The heating pump (secondary side) connected to the cascade module runs for the time set here longer than for the
heat requirement.
Flow temp. peak load 30 ... 50 ... 70 °C In the control strategy "Serial cascade with peak load coverage" (coding card at position 3), the heat source
necessary to cover the peak load is connected when the flow temperature required by the controls exceeds the
value set here.
Outside temp. Peak load – 20 ... 10 ... 20 °C In the control strategy "Serial cascade with peak load coverage" (coding card at position 3), the heat source
necessary to cover the peak load is connected when the outside temperature falls below the value set here.
Start-up delay Next device 0 ... 6 ... 30 min Once a heat source is connected, the controls wait for the time set here until the next device is connected.
Tolerated overtemp. 0 ... 5 ... 10 K To reduce the device cycles, the heat sources are only turned off when the flow temperature exceeds the desired
set temperature by the tolerated overtemperature (positive switching differential).
Tolerated undertemp. 0 ... 5 ... 10 K To reduce the device cycles, the heat sources are only turned on when the flow temperature falls below the desired
set temperature by the tolerated undertemperature (negative switching differential).
Table 6
18


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus MC 400 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus MC 400 in the language / languages: English, German, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 4,41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info