10 Troubleshooting
Logano plus GB402 – 6 720 804 428 (2012/09)
49
B 8L 534 No gas pressure
or additional flue
gas pressure
limiter (pressure
> 7.5 bar) has
responded.
There is no gas
pressure although
solenoid valve 1 should
have opened. The
burner makes three
successive attempts at
starting, then there is a
delay of one hour,
before making three
more start attempts.
Check that the gas tap is open. Replace the gas train if
required.
Check whether there is gas
pressure.
Check the gas pressure.
Check whether the flue gas
pressure limiter has responded.
Reset the flue gas pressure
limiter.
Check the flue gas path for
blockages.
Check electrode. Replace electrode if required.
Check ignition transformer. Replace ignition transformer if
required.
Check gas filter for
contamination.
Replace gas filter if required.
V 8P 580 Solenoid valve 1
leaking
The valve test system
has detected an
unacceptably high
leakage rate on
solenoid valve 1.
Check gas train for
contamination.
Gas filter fitted.
Replace gas train.
V 8U 581 Solenoid valve 2
leaking
The valve test system
has detected an
unacceptably high
leakage rate on
solenoid valve 2.
Check gas train for
contamination.
Gas filter fitted.
Replace gas train.
V 9Y 500
501
502
503
Internal SAFe
relay faulty.
Internal SAFe
electronics faulty.
Press "Reset" and wait to see if
the fault has been removed.
Replace the SAFe if the fault
persists after "Reset" has been
pressed.
V CY 566 Return
temperature
<-C
(interruption)
The control unit
receives unrealistic
values from the return
sensor.
Check cabling between SAFe and
return sensor.
Check electrical connection of the
SAFe cable.
Replace cable if required.
Remedy contact problem if
required.
Replace temperature sensor if
required.
Check resistance values of
temperature sensor according to
table.
Check voltage at the temperature
sensor terminals inside the SAFe
according to table.
Replace SAFe if resistance
values of the temperature
sensor are correct, but voltage
values are incorrect.
V CY 567 Return
temperature
> 130 °C (short
circuit)
The control unit
receives unrealistic
values from the return
sensor.
Check cabling between SAFe and
return sensor.
Replace cable if required.
Check electrical connection of the
SAFe cable.
Remedy contact problem if
required.
Check resistance values of
temperature sensor according to
table.
Replace temperature sensor if
required.
Check voltage at the temperature
sensor terminals inside the SAFe
according to table.
Replace SAFe if resistance
values of the temperature
sensor are correct, but voltage
values are incorrect.
V CO 568 Water pressure
sensor fault
(cable break).
Water pressure sensor
interruption (voltage
>3.5V).
Check lead to water pressure
sensor.
Check water pressure sensor.
Remedy any interruption.
Replace water pressure
sensor.
V CO 569 Water pressure
sensor fault
(short circuit).
Water pressure sensor
short circuit (voltage
<0.5V).
Check lead to water pressure
sensor.
Remedy any short circuit.
Check water pressure sensor. Replace water pressure
sensor.
Type
1)
Display
code
Fault code Cause Description Test procedure/cause Correction
Tab. 22 Fault displays
1) V = locking; B = blocking
49


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus Logano plus GB402 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus Logano plus GB402 in the language / languages: English as an attachment in your email.

The manual is 5,41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus Logano plus GB402

Buderus Logano plus GB402 User Manual - English - 20 pages

Buderus Logano plus GB402 User Manual - German - 2 pages

Buderus Logano plus GB402 Installation Guide - Dutch - 60 pages

Buderus Logano plus GB402 User Manual - Dutch - 16 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info