Logamatic EMS RC35 programming unit - Subject to technical modifications
31
System settings (Service menu – Settings)
6
6.3.1 Assignment of programming unit/remote control unit in the software
This function is not available with boilers with UBA1.x and DBA.
Example: heating system with heating circuit 1 and heating circuit 2 (Æ page 11)
6.3.2 Control mode (outside temp. contr./room influence)
The temperature of the heating water in the boiler is defined by the heating curve in the Logamatic
control unit. You can select whether this heating curve will be influenced solely by the outside
temperature, or by a mixture of outside temperature and room temperature.
outside temp. contr.: If this setting is entered, the boiler temperature calculated in the control
unit will be regulated by variation in the adjusted outside temperature in combination with
selected settings for set room temperature, offset, design temperature and minimum outside
temperature. This temperature is then delivered to the radiators or underfloor heating system by
means of permanent operation of the heating circuit pump.
The only circumstances in which this setting can result in the heating circuit pump being
switched off are summer mode, night setback (subject to the selected setback mode) or DHW
mode (only with DHW priority).
outside temp. contr. with room temperature hook-up (factory setting): this form of control
functions like a pure weather-compensated control with the difference that parameter maximum
room influence enables the determination whether and to what extent the room temperature
can influence the heating curve.
The programming unit/remote control must be installed in a reference room to ensure that a
representative room temperature is captured.
The higher the parameter is set, the higher the proportion of the room temperature effect on the
heating curve (factory setting 0 Kelvin). This applies when the room temperature exceeds or falls
below the set room temperature. If the maximum room influence parameter is set to 0, the
heating characteristics will be controlled solely by outside temperature.
Alternative
Setting: Which operating unit is
assigned to the heating circuit?
Effect
A HC 1 = RC35, HC 2 = RC35
(Æ Fig. 2, [1], page 11)
Same room temperatures for HC 1 and
HC 2
B HC 1 = none, HC 2 = RC35
(Æ Fig. 2, [1], page 11)
Room temperatures for HC 1 and HC 2
can be set separately
C HC 1 = RC2x, HC 2 = RC35
(Æ Fig. 2, [2], page 11)
Room temperatures for HC 1 and HC 2
separately adjustable;
adjust the room temperature for HC 1 at
the RC2x
Tab. 13 Settings for room temperature depending on programming unit
31


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus Logamatic EMS RC35 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus Logamatic EMS RC35 in the language / languages: English as an attachment in your email.

The manual is 2,02 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus Logamatic EMS RC35

Buderus Logamatic EMS RC35 User Manual - English - 60 pages

Buderus Logamatic EMS RC35 Installation Guide - German - 60 pages

Buderus Logamatic EMS RC35 User Manual - German - 60 pages

Buderus Logamatic EMS RC35 User Manual - Dutch - 60 pages

Buderus Logamatic EMS RC35 Installation Guide - Dutch - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info