System settings (Service menu – Settings)
Logamatic EMS RC35 programming unit - Subject to technical modifications
30
6
What is the desired
maximum flow
temperature?
25 °C to 60 °C 45 °C
2)
For how many days
should maximum flow
temp. be maintained?
0 days to 20 days 4 days
2)
Every how many days
should the flow temp.
be reduced?
direct normal
operat., every day,
every 2nd day to
every 5th day
Every day
2)
By how many K should
the flow temp. be
reduced each time?
0 K to 20 K 5 K Adjustment only if, for flow
temperature reduction,“direct normal
operat.” has not been selected.
4)
Do you wish to change
the switching
programme?
yes, no no When selecting “yes” the system
jumps to the heating circuit
switching program.
Should the switching
programme be optimised?
yes, no no Start and stop times are
automatically adjusted according to
the outside temperature, room
temperature and building type (heat
storage capacity).
What reduction mode
should be used for
holiday?
Outdoor setback
mode,
reduced operation,
Room setback
mode, shut-down
mode
Outdoor
setback
mode
See page 33.
Adjustment “Room setback mode”
only if a remote control (e.g. RC2x)
has been allocated to the heating
circuit.
If “reduced operation” has been
selected, the standard night temper-
ature will be applied.
What outside temp.
should be used?
– 20 °C to
+10 °C
5 °C Temperature threshold for outdoor
setback mode (Æ page 33).
Adjustment only if setback mode for
holiday was set to “Outdoor setback
mode.”
1) The setting range can be limited, subject to boiler.
2) Not possible or available on boilers with UBA1.x or DBA.
Menu item Input range
Factory
setting Other information
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Buderus Logamatic EMS RC35 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Buderus Logamatic EMS RC35 in the language / languages: English as an attachment in your email.

The manual is 2,02 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Buderus Logamatic EMS RC35

Buderus Logamatic EMS RC35 User Manual - English - 60 pages

Buderus Logamatic EMS RC35 Installation Guide - German - 60 pages

Buderus Logamatic EMS RC35 User Manual - German - 60 pages

Buderus Logamatic EMS RC35 User Manual - Dutch - 60 pages

Buderus Logamatic EMS RC35 Installation Guide - Dutch - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info