Section 6 Faults
When the control in the Evap detects a fault, this is displayed at the bottom of the product by the alarm symbol
(bell) by means of an LED. To reset the alarm the product must be briefly disconnected from the power supply by
removing the plug from the socket and then replacing this in the socket after 10 seconds. A TEST cycle of
approximately 3 minutes will start, during which the service LED flashes. The light stops flashing when the test is
over. The Table¹ below shows different causes of an alarm and the repair or control action.
Alarm LED
Meaning
Action
Reset
Alarm LED on
Contact System
On/Off broken,
unit switches off
Restore contact System On/Of, see wiring diagram
Automatic
Alarm LED blinks
3 times
Contact with
SHC80 sensor
broken
Check SHC80 wiring and if necessary repair, check that
the light on SCH80 sensor flashes regularly, if not replace
faulty sensor.
Automatic
Alarm LED blinks
5 times
T3 sensor
outside air faulty
Check wiring for break or wear, in case of doubt replace
sensor.
Automatic
Alarm LED blinks
9 times
There is no
increase in
channel RH%
(T1 SHC80), for
a period of 3
hours. The unit
turns off.
- Check if the water tap is open.
If the tap is open and there is a demand (outside
temperature below 12 ° C) check the strainer in the
connection coupling, it must be clean.
- Check the functioning of the water valve. Disconnect the
black supply hose from the knee on the unit, and reset
the unit by plugging out and plugging in again; if water
comes out and the water valve and this stops after 90sec,
then the valve is OK, the water keeps flowing or no water
comes out of the hose, then the water valve is defective,
replace the water valve. If the water valve works and the
matrix does not get wet after the valve has switched, the
legionella filter is clogged; replace the cassette.
If the matrix does get wet and still has an alarm, the
matrix is contaminated and the cassette must be
replaced. Product No .: 351025
Automatic
Alarm LED blinks
15 times
Heating faulty
Check air temperature after the humidifier, this must be
>8ºC, if not air heater is faulty. Call installer for
replacement.
Automatic
Alarm LED blinks
17 times
No airflow
Check if HRV is working. If this works, the matrix is
contaminated and must be replaced. Product No .:
351025
Automatic
Alarm LED blinks
19 times
T2 sensor faulty
Check wiring for break or wear, in case of doubt replace
sensor.
Automatic
Service LED
continuously on
The cassette
must be replaced
To be able to humidify safely it is necessary to
replace the complete cassette; Order product code
351025 from your dealer.
In the interim, you can reset the service alarm at the
bottom by pressing and holding the reset button for
30 seconds. The opening is located next to the
service LED.
ATTENTION the LegioSafe filter will soon become
obstructed, after which proper and safe operation is
no longer guaranteed!!
Reset the service alarm
at the bottom by
pressing and holding the
reset button for 30
seconds. The opening
is located next to the
service LED.
41


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Brink Evap at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Brink Evap in the language / languages: English, German, Dutch, French as an attachment in your email.

The manual is 3,37 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info