Control unit
27
Uni Condens 8000 F – 6720867056 (2016/10)
Secure all cables with cable clips (supplied with the control unit):
Insert the cable clip together with the cable from above into the
slots in the frame ( fig. 27, page 27).
Slide the cable clip downwards.
Counterhold.
Flip the lever up.
Fig. 27 Securing a cable with a cable clip
Refit the cover hood on the control unit ( fig. 7.2.1, page 26).
Secure the control unit cover hood by tightening the screws
( fig. 25, page 26).
7.2.3 Control unit settings
If a control unit from the CFB 800/CFB 900 series is used, burner
modulation in standard mode is not enabled for 2.5 minutes.
Avoid fast upwards modulation.
Regulator settings
Table 12 Adjustable parameters for CFB 810 and CFB 840
Set boiler temperature controller and maximum boiler temperature
The boiler temperature controller ensures emergency operation with an
adjustable boiler water temperature if the control electronics fail. In
standard control mode, the maximum boiler temperature adopts the
function of the boiler temperature controller. The maximum boiler water
temperature can be selected in the control unit in the "Boiler
parameters" menu, under menu item "Max. shutdown temperature".
Control unit settings
Fig. 28 Control unit settings
[1] High limit safety cut-out
[2] Temperature controller
[3] MEC2
Select temperatures ( tab. 12, page 27) at high limit safety cut-out
[1] in the control unit and at temperature controller [2].
Select the maximum boiler water temperature at the MEC2 [3].
The maximum temperature demand is not a value that is set directly. The
maximum temperature demand is composed of the set temperature and
the rise.
Example DHW demand:
Sum of the set DHW temperature (60 °C) and the parameter "return
temperature increase" (20 °C) in the "DHW" menu:
60 °C + 20 °C = maximum temperature demand 80 °C.
Example heating circuits:
Sum of the set temperature of the heating circuit with mixer with the
highest temperature required (70 °C) and the parameter "return
temperature increase" (5 °C) in the "Heating circuit data" menu:
70 °C + 5 °C = maximum temperature demand 75 °C.
All maximum temperature demands must always be 7 K below the
maximum selected boiler water temperature.
Adjustable
parameter
(max. temperature)
CFB 810 CFB 840
High limit safety cut-
out (STB)
1)
1) Set the high limit safety cut-out and temperature controller as high as possible,
but ensure the settings are at least 5 K apart.
110 °C 110 °C
 at least 5 K
Temperature
controller (TR)
1)
105 °C 90 °C
 at least 6 K at least 18 K
Max. boiler water
temperature
99 °C 84 °C
 at least 7 K
Max. temperature
demand
2)
of heating
circuit
3)
and DHW
4)
2) Both temperature demands must always be at least 7 K under the maximum
boiler temperature.
3) The temperature demand of heating circuits equipped with an actuator is
composed of the set flow temperature and the "return temperature increase"
parameter in the heating circuit data menu.
4) The temperature demand of DHW heating is composed of the set DHW
temperature and parameter "return temperature increase" in the DHW menu.
92 °C 77 °C
6720615883-31.1RS
.
.
.
.
.
0010011563-001
1 2 3
80
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Uni Condens 8000 F at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Uni Condens 8000 F in the language / languages: English as an attachment in your email.

The manual is 10,41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch Uni Condens 8000 F

Bosch Uni Condens 8000 F User Manual - English - 12 pages

Bosch Uni Condens 8000 F User Manual - German - 16 pages

Bosch Uni Condens 8000 F User Manual - Dutch - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info