14 | Mounting
MC 4006 720 816 739 (2015/05)
2.6 Additional accessories
For detailed information about suitable accessories, please refer to the
catalogue.
User interface: weather-compensated controller with outside
temperature sensor or room temperature-dependent controller;
connect to BUS (do not connect to BUS1, BUS2, BUS3 or BUS4);
connect outside temperature sensor to T1
Flow temperature sensor; connect to T0
Outside temperature sensor; connect to T1
Return temperature sensor; connect to T2
Cascade pump; connect to PC0
Heating pump; connect to PC1
Switch for max. output; connect to I2
Stop switch; connect to I3
IGM for heat source without EMS, EMS 2 or EMS plus; connect in
accordance with the technical documentation for the IGM (the
MC400 cascade module replaces the ICM)
Installation of additional accessories
Install the additional accessories in accordance with legal
requirements and the instructions supplied.
2.7 Cleaning
If required, wipe the enclosure with a damp cloth. Never use
aggressive or acidic cleaning agents for this.
3Mounting
3.1 Installation
Install the module on a wall, ( Fig. 6 to Fig. 8, starting at page 82),
on a mounting rail ( Fig. 9, page 82) or in an assembly.
When removing the module from the mounting rail, refer to Fig. 10 on
page 83.
3.2 Electrical connection
Observe current regulations applicable to power connections, and
use at least cable type H05 VV-…
3.2.1 Connecting the BUS connection and temperature sensor
(extra-low voltage side)
General BUS connection
Maximum total length of BUS connections:
100 m at 0.50 mm
2
conductor cross-section
300 m at 1.50 mm
2
conductor cross-section
BUS connection between the heat source – and cascade module
Connect the heat sources and lower-level cascade modules directly to
terminals
BUS1 ...BUS4
(
overview of the terminal assignment).
BUS connection between the cascade module – user interface
other modules
If the conductor cross-sections are different, use the junction box to
connect the BUS nodes.
BUS user [B] via junction box [A] in a star ( Fig. 19, page 84, note
the instructions for the user interface and other modules).
Temperature sensor
When sensor leads are extended, apply the following lead cross-sections:
up to 20 m with 0.75 mm
2
to 1.50 mm
2
conductor cross-section
20 m up to 100 m with 1.50 mm
2
conductor cross-section
Maximum output per connection
•PC0, PC1
•A0, IA1
400 W (high-efficiency pumps
permitted; max. 40 A/s)
•10W
Capturing range for the flow and
return temperature sensor
Lower fault limit
Display range
Upper fault limit
< – 10 °C
0 ... 100 °C
> 125 °C
Capturing range, outside
temperature sensor
Lower fault limit
Display range
Upper fault limit
< – 35 °C
– 30 ... 50 °C
> 125 °C
Permitted ambient temp. 0 ... 60 °C
IP rating IP44
Protection class I
ID no. Data plate ( Fig. 22, page 85)
Specifications
Table 3
DANGER: Risk of electric shock!
Before installing this product: completely disconnect
heat appliances and all other BUS nodes from the mains
voltage.
Before commissioning: fit the cover ( Fig. 21,
page 85).
If the maximum cable length of the BUS connection between
all BUS nodes is exceeded, or if the BUS system is realised
as a ring structure, the system cannot be commissioned.
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch MC 400 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch MC 400 in the language / languages: English, German, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 4,41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info