ADVANCED MENU
6 720 806 630 (2013/02)10
10.3.2 HOT WATER PEAK DHW (ANTI LEGIONELLA)
Pasteurisation is set in Hot water peak. If you set the interval to 7 days,
for example then the DHW temperature is raised to approx. 65 °C every
seventh day.
Fig. 19
Select menu option Hot water peak.
▶Select Interval.
Set required interval. Minimum = 0, maximum = 28 days.
▶Select Save to save the change or Cancel to return without saving.
With Start time you determine when pasteurisation should commence.
10.3.3 HOT WATER TEMPERATURE
Hot water, maximum operating time at heating demand is used for
setting the maximum operating time for DHW when heat is required.
Select the Hot water temperature.
Select the Hot water, maximum operating time at heating
demand.
Set the duration of the function by choosing the number of hours.
Minimum = 0, maximum = 60 minutes.
▶Select Save to save the change or Cancel to return without saving.
10.3.4 TIME CONTROL HOT WATER
Time control hot water is used to disable hot water heating completely
to save energy. This is primarily effective when peak tariffs (high price
for energy consumption) are charged, but also gives limited access to
hot water. This is done in the same way as with the other heat pump time
controls.
10.3.5 TIME CONTROL HOT WATER CIRCULATION
The time control for the DHW circulation pump is set under Advanced.
▶Under Advanced.
▶Select Hot water.
▶Select Time control hot water.
A switch-on and switch-off can be set for each day of the week.
10.4 TIMERS
Fig. 20
The controller has several time programs. The status of the time
programs is displayed in the Timers menu. Only activated functions are
displayed in the menu. The others are hidden until activation.
EXTRA HOT WATER
Displays the remaining time for requested extra hot water.
ADDITIONAL HEAT START
Displays the countdown of the timer for delay of additional heat.
MIXING VALVE CONTROL DELAY
Displays the time that the mixing valve function is delayed after the
additional heat timer has counted down.
ALARM MODE DELAY
Displays the remaining time until the additional heat is activated when an
alarm is triggered.
COMPRESSOR START
Displays remaining time of compressor start delay.
HEATING, OPERATING TIME AT HOT WATER DEMAND
Displays the remaining time before the maximum time in heating mode
is reached if there is a simultaneous hot water requirement.
HOT WATER, OPERATING TIME AT HEATING SYSTEM DEMAND
Displays the remaining time before the maximum time for hot water
production is reached if there is a simultaneous heating requirement.
10.5 SETTING THE CLOCK
The heat pump has functions that are dependent on both the time and
date. Thus it is important that these are correct.
10.5.1 SET DATE
Setting the date:
▶Select Setting the clock in the extended menu.
Fig. 21
Select the Set date.
Set the correct date with the menu dial. Use the form Year-Month-Day
(yy/mm/dd).
▶Select Save to save the change or Cancel to return without saving.
10.5.2 SET TIME
Set the time:
▶Select Setting the clock in the extended menu.
Fig. 22
Select the Set time.
Set the correct time with the menu dial. Use the form
Hour:Minute:Second.
▶Select Save to save the change or Cancel to return without saving.
10.6 ALARM
Any triggered alarms and warning displays are stored, together with the
time of their occurrence, in Alarm log. If an alarm symbol is shown on
the display, the alarm is still active and steps are required accordingly. (
chapter 13).
This function is only used when a secondary hot water
circulation pump is installed.
6 720 648 149-21.1I
6 720 648 149-22.1I
6 720 641 467-55.1I
6 720 641 467-56.1I
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Greensource Hydrolight - Hydrocomfort at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Greensource Hydrolight - Hydrocomfort in the language / languages: English as an attachment in your email.

The manual is 1.66 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info