Commissioning
Condens 7000 WP – 6721841195 (2022/01)
22
8 Commissioning
WARNING
Escaping gas.
After completing the work, check the tightness of all gas-carrying
components.
CAUTION
Flue gas spillage.
Check the tightness of all flue gas routing parts once the work is
complete.
Complete the commissioning report during the commissioning
procedure (§ 15.7, p. 50).
8.1 Commissioning the boiler
NOTICE
Risk of boiler damage due to unsuitable fill water.
Check the chloride content of the fill water, if the maximum heating
water temperature is set higher than 80 °C ( § 5.4, p. 12).
Check whether the fill water satisfies the water quality requirements
( § 5.3, p. 12).
The boiler starts as soon as the operating pressure exceeds 0.8 bar.
If the operating pressure is lower than 0.2 bar, the appliance no longer
goes into operation.
Open all radiator valves.
Check whether the service shut-off valves of the connection sets are
open.
Use an appropriate filling method in line with Water Regulations.
(
§ 2.11, p. 6).
Fill the heating system to a pressure of 2 bar and close the filling
valve.
Vent the radiators.
Fill the heating system again to a pressure of 2 bar.
Open the gas cock.
Venting the gas line.
Operate the appliance.
Start up the boiler.
8.2 Setting the parameters
Different parameters can be set in the settings menu so the
boiler can be adapted to the heating system.
Go through the parameters in the menu Settings ( § 9.4, p. 26).
Adjust the parameters if required.
Make a note of which parameters have been modified in the
commissioning report ( § 15.7, p. 50).
Setting Maintenance type
With a maintenance period of 2 years, normal operation is considered to
be a maximum burner runtime of 4000 hours (every 2 years). During
commissioning, the anticipated burner runtime must be estimated in
order to set the right Maintenance type. During the initial inspection or
maintenance the burner runtime can be read out via the service menu
and the burner runtime Maintenance type modified if required.
Open the menu Maintenance > Maintenance type.
Based on the operation, estimate whether the maximum burner
runtime of 4000 hours will be exceeded in 2 years.
If the maximum burner runtime of 4000 hours in 2 years is likely to be
exceeded:
Set Burner run time to 4000 hours.
If the maximum burner runtime is likely to be less than 4000 hours:
Set Boiler run time to 24 months.
-or-
Set Service date: 24 months after installation date.
Table 8 Maintenance interval parameters
Setting Min. boiler outp.
If the boiler is installed in a positive pressure cascade system, the
minimum load must be increased.
Open the menu Limit values > Min. boiler outp..
Increase the setting Min. boiler outp. ( table 9).
Table 9 Setting the Min. boiler outp. with positive pressure cascade
systems
Setting Maintenance
type
Burner run
time
Boiler run
time
Service date
Standard operation 4000 hours 24 months Date: 24
months after
installation
Factory Raised value with
positive pressure
cascade
Appliance type: [%] [%]
GC7000WP 50 28 36
GC7000WP 65 20 26
GC7000WP 85 24 28
GC7000WP 100 20 23
22


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Condens GC7000WP at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Condens GC7000WP in the language / languages: English as an attachment in your email.

The manual is 15.02 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch Condens GC7000WP

Bosch Condens GC7000WP User Manual - English - 12 pages

Bosch Condens GC7000WP Installation Guide - German - 60 pages

Bosch Condens GC7000WP User Manual - German - 12 pages

Bosch Condens GC7000WP Installation Guide - Dutch - 56 pages

Bosch Condens GC7000WP User Manual - Dutch - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info