Operation without the outdoor unit (individual operation)
Compress 3400i AWS – 6721852066 (2023/01)
20
6.4 Pressure switch and overheating protection
The pressure monitor and overheating protection are only installed in
indoor units with integrated electric booster heater.
The pressure switch and overheating protection are connected in series.
Alarms or information triggered at the control unit indicate either that
the operating pressure is too low, or that the temperature of the electric
booster heater is too high.
NOTICE
Material damage from running dry!
When the primary circulation pump PC0 is operated for a long time when
the operating pressure is too low, it can be damaged.
Eliminate any leaks in the system that are indicated when the
pressure switch is triggered.
The triggering of the pressure switch only blocks the electric booster
heater. The primary circulation pump PC0 and the outdoor unit can
continue to run if there is a risk of frost.
Pressure switch
The indoor unit has a pressure switch which triggers once the pressure in
the heating system falls below 0.5 bar. Once the pressure exceeds
0.5 bar, the pressure switch is automatically reset.
Make sure that the expansion vessel and pressure relief valve are
configured for the indicated operating pressure, and check whether
an additional expansion vessel is necessary in the system.
Check the system for leaks, and use a larger expansion vessel if
necessary.
Slowly increase the pressure in the heating system by adding water
through the fill valve.
Overheating protection
The overheating protection triggers when the temperature of the electric
booster heater rises above 95 °C.
Check the operating pressure.
Check the heating and DHW settings.
Reset the overheating protection. To do this, press the button on the
terminal box.
6.5 Function test
Start the system according to the instructions for the control unit.
Vent the system according to chapter 6.2.
Test the active components of the system as described in the
instructions for the control unit.
Check if the start conditions have been met for the outdoor unit.
Check if there is a heating or hot water demand.
-or-
Draw off DHW or increase the heating curve to generate demand (if
necessary, adjust the setting for Heating mode down if the outside
temperature is high).
Check if the outdoor unit starts.
Make sure that there are no current alarms (see instructions for the
control unit).
-or-
Eliminate any faults according to the control unit instructions.
Check the operating temperatures in accordance with the
instructions for the control unit.
6.5.1 Operating temperatures
The operating temperature check must be performed in heating mode
(not in DHW or cooling mode).
For optimum system operation, the flow rate in the heat pump and
heating system must be monitored. This check should be performed
when the heat pump is operating for more than 10 minutes and during
high compressor heating output.
The temperature differential for the heat pump must be set for the
different heating systems.
With underfloor heating system 5 K as temp.diff. Setting heating.
With radiators 8 K as temp.diff. Setting heating.
These settings are optimal for the heat pump.
Check the temperature differential at high compressor heating output:
Open the diagnosis menu.
Select Monitored values.
Select Heat pump.
Select Temperatures.
Read the primary flow temperature (heat transfer medium out,
sensor TC3) and return temperature (heat transfer medium in,
sensor TC0) in heating mode. The flow temperature must be higher
than the return temperature.
Calculate the difference TC3–TC0.
Check whether the difference corresponds to the delta value set for
heating mode.
If the temperature differential is too large:
Vent the heating system.
Clean filters / strainers.
Check pipe dimensions.
Temperature differential in the heating system
Set the output at the heating pump PC1 so that the following
difference is achieved:
With underfloor heating system: 5 K.
With radiators: 8 K.
7 Operation without the outdoor unit (individual
operation)
The indoor unit can be started without the outdoor unit being connected,
for example if the outdoor unit is to be installed at a later date. This is
termed individual operation or stand-alone operation.
With individual operation, the indoor unit only uses the integrated or
external auxiliary heater for heating and DHW heating.
Commissioning in individual operation:
▶In the «Heat pump» service menu, select the option «Stand-alone
mode» ( instructions for the control unit).
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Bosch Compress 3400i AWS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Bosch Compress 3400i AWS in the language / languages: English as an attachment in your email.

The manual is 7.89 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Bosch Compress 3400i AWS

Bosch Compress 3400i AWS User Manual - English - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info