Before testing an RCD, the 4 mm safety plug of the test cable must be
disconnected from the test socket
9
.
Measurement might be influenced by:
- a possibly existing voltage between the protective conductor of the
shockproof socket and earth
- leakage currents in the circuit behind the RCD
- further earthing equipment
- equipment which is connected behind the RCD and which will cause a
longer tripping time, e.g. capacitors or rotating machines
9.5.1 Testing of permanently installed RCDs
- Connect the IEC power cord to the IEC connector J of the BENNING ST 725.
- Connect the shock-proof plug to a shock-proof socket which is protected by the RCD to be
tested and switch on the RCD.
- Press the -key
6
to start the RCD test.
- If the "rESET" symbol is still shown on the display and the "LN" and "LE" symbols are
flashing, turn the shock-proof plug in the shock-proof socket by 180° and press the -key
6
again to start the test.
- Whenever the "rESEt" symbol appears on the display, switch the RCD on again.
- The BENNING ST 725 generates a fault current of 30 mA with positive (0°) or negative
(180°) initial polarity. The RCD trips and the tripping times of the one-fold nominal fault
current are measured.
- If the tripping time is less than the limiting value (200 ms), a will be shown next to the
tripping time.
- Subsequently, the BENNING ST 725 generates a fault current of 150 mA with positive (0°) or
negative (180°) initial polarity. The RCD trips and the tripping times of the five-fold nominal
fault current are measured.
- If the tripping time is less than the limiting value (40 ms), a will be shown next to the
tripping time.
- The test is considered to be passed, if "PASS" is shown on the display.
Seegure8a: TestingofpermanentlyinstalledRCDs(I
ΔN
=30mA)
Note:
- By generating a fault current of 30 mA, it is proven that the RCD will trip when the nominal
fault current is reached. If the limiting value of the maximum contact voltage of 50 V is
exceeded, the "UB > 50 V" symbol will be shown on the display and the testing will be
stopped.
Measurement might be influenced by:
- a possibly existing voltage between the protective conductor of the
shockproof socket and earth
- leakage currents in the circuit behind the RCD
- further earthing equipment
- equipment which is connected behind the RCD and which will cause a
longer tripping time, e.g. capacitors or rotating machines
9.5.2 Testing of portable RCDs (PRCDs)
- Connect the plug of the mains connection cable to the jack K of the BENNING ST 725.
- Connect the shock-proof plug to a 230 V shock-proof socket. With the mains voltage being
applied, the voltage measurement will start automatically.
- Depending on the external conductor position (right or left) of the shock-proof socket, the
voltage potentials between the connecting terminals L, N and PE will be shown on the
display for approx. 2 seconds.
45


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Benning ST 725 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Benning ST 725 in the language / languages: English, German, French as an attachment in your email.

The manual is 10,68 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info