Arrangement with 4 m feeder
4000 5820 2966 2374 114
Arrangement with 5 m feeder
5000 6805 3951 2374 -60
* Dimension "A" is specified by the client when ordering based on spatial layout of the specific
boiler room.
4.2. Control and safety elements of the boiler
Control and regulation of the boiler is ensured by a control unit - see separate instruction
manual.
Safety components that monitor the safe operation of the boiler:
The emergency thermostat is used to prevent the system from overheating. The
manufacturer sets the thermostat at 95 °C, i.e. at a higher temperature than the setpoint that
can be set on the boiler. The emergency thermostat is positioned on the rear wall of the
boiler in the control unit cabinet.
Thermal protection of the motor (thermal contact) is part of both fuel feeder motors and is
used to protect them from overheating in the case of fuel feeder blockage. It also
retroactively stops the fan, so as to avoid burning of the fuel in the container in the event of
a fault. During normal operation, the motor working temperature is up to 85 °C - such
warming does not mean a failure.
The turnstile is a device that mechanically separates the fuel between the screw conveyors
(feeding from the bunker + feeding into the boiler). In the event of re-ignition of the fuel in
the boiler feeding (e.g. during power outage for a longer time) the fuel in the tank does not
ignite. Furthermore the turnstile serves as a partial fuel crusher, so in the event that a longer
piece reaches the turnstile, the turnstile crushes this piece into smaller ones.
The cover limit switch of the bunker feeder shuts down the screw feeder and fan when the
cover is open. After its proper closure the boiler is put back into operation.
The emergency fire extinguishing system is another security feature preventing burning of
fuel through to the container. A temperature increase above 95 °C at the feeding out of the
bunker results in thermostatic valve opening and the space is cooled with cooling water
from the water main.
Firing flap is located between the second and the third draft in the top part of the boiler body
and serves to regulate the flue gas temperature at the boiler outlet.
When operating the boiler when the flue gas temperature is higher than 100 °C the firing
valve must be closed, i.e. firing flap lever on the side of the boiler must be rotated as much
as possible forwards and secured with a locking screw. When firing (with cold chimney) or
during long term operation of the boiler at lower output it is recommended to operate the
boiler with the firing valve slightly open so that the flue gas temperature does not drop
below 80 °C. In this case, the firing flap lever must be rotated downward (backwards) and
secured by a locking screw.
4.3. Boiler accessories
Standard accessories:
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Benekov S100 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Benekov S100 in the language / languages: English as an attachment in your email.

The manual is 1,02 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info