9 | Installation instructions EN Operating manual Fireplace inserts slied flat + II
64
9.11 Ceiling above the fireplace insert
G
8
11
Fig.14: Ceiling above fireplace insert
If the cavity above the fireplace insert reaches as far as the
room ceiling (8), then the latter must be protected if:
it consists of flammable components
it serves as a bearing component
The thermal insulation layer (11) (dimension G) must be ex-
ecuted in compliance with the normal regional installation
standards.
8 Room ceiling
11 Heat insulation layer
9.12 Floor in front of the fireplace insert
The floor in front of the fireplace insert must be made of flammable material. Minimum dimensions of
this non-flammable area: forward at least 50cm, to the sides at least 30cm.
9.13 Fire protection
Fire protection within the radiation area
The minimum clearance (see Technical Data) to components made of flammable construction materi-
als or flammable components as well as furniture must be observed in front and on either side of the
firebox opening! For II series models the clearance applies to the front and rear.
Fire protection outside the radiation area
From the outer surfaces of the cladding of the open fireplace insert a distance of at least 5 cm must be
maintained from components made of flammable construction materials or flammable components
and from built-in furniture. The clearance space must be so open to the air current that an accumula-
tion of heat cannot occur. Components which only cover small areas of the cladding of the open fire-
place insert (such as floors, butt-joined wall cladding and insulation layers on ceilings and walls) can be
brought up to the cladding without any gap.
9.14 Heat insulation layers and materials
Insulation layers must be made of heat insulating boards of construction material class A1 as per DIN
4102 Part 1 with a maximum application temperature of at least 700°C and a bulk density of more
than 80kg/m³. The insulation material must be marked with the appropriate insulation material code
number as per AGI-Q 132. Only the insulation materials which are listed in the following table may be
used. If other insulation materials are used for the insulation layers, these must have an appropriate
DIBT approval (German Institute for Structural Engineering Berlin) (e.g.: Promat calcium silicate
thermal insulating board “Promasil950KS”, Wolfshöher thermal insulating board “Prowolf”, Wolf-
shöher thermal insulating board “Vermilite2000”, Thermax thermal insulating board “Ther-
maxSN400”). For building external walls and ceilings to be protected that have a U-value below
0.4W/m², additional rear ventilation (see technical rules of the Stove- and Air Heating Constructors As-
sociation) will be necessary.
64


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II in the language / languages: English as an attachment in your email.

The manual is 14.06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II

Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II User Manual - German - 124 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info