9 | Installation instructions EN Operating manual Fireplace inserts slied flat + II
62
9.3 Convection space
54
16
Fig.10: Convection space
If the convection cladding (appliance part) is not used, a
convection space of at least 6 cm depth between fire-
place insert (4) and insulation layer (16) to the rear and
on both sides must be allowed for.
The convection space (5) must be heat-insulated to all
areas that are not heat-emitting claddings.
The walls, the floor and the ceiling of the heating cham-
ber must be clean and resistant to abrasion (see tech-
nical rules of the stove- and air heating constructors as-
sociation). Therefore the insulation layer, if it is not cal-
cium silicate slabs, must be protected with an abrasion-
resistant material (heat shield/heating chamber plate or
similar).
4 Convection space between fireplace insert and insulation
layer
5 Convection space
16 Insulation layer
Convection air duct with convection cladding
All convection air ducts must be made of dimensionally stable, non-flammable construction materials.
The warm air pipes must be fixed firmly to the warm air-/(supply) collar of the convection cladding and
the grilles (optimally with collar plate).
9.4 Convection conduction
3 0 c m
c m
30 cm
50 cm
13
14
Fig.11: Convection conduction
You can find the cross-section for the air outlet (14) and
air inlet (13) in the technical catalogue, the product data
sheet from the homepage or the Technical Data section
in this manual.
Above at least 200cm², air inlet and air outlet must not
be lockable.
There must be no flammable construction materials,
e.g. wooden ceiling, and no furniture within a range of
30cm next to and 50cm above the air outlets (14).
13 Air inlet
14 Air outlet
62


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II in the language / languages: English as an attachment in your email.

The manual is 14.06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II

Austroflamm Fireplace inserts slied flat II - Kamineinsatz Schieb flach II User Manual - German - 124 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info