5.4.8 CONNECTION TO THE ACCUMULATION TANKS
System of the connection is based on warming the accumulation tanks, where is the accumulated
warmth from accumulation tanks gradually drained according to the requirements of heated space. Dur-
ing the bioler operation at full output are accumulation tanks warmed at 80–90 °C. Heating with accu-
mulation tanks in connection with ATTACK SLX boiler brings several advantages. Main advantages are
higher efficiency, lower fuel consumption, prolonged lifetime of the boiler, more frequent operation,
minimal creation of acids and condensates, higher comfort, lower risk of boiler overheating and fuel sav-
ing.
Recommended volume of the accumulation tank for ATTACK SLX 25 boiler is 2000 l (for other outputs
see technical parameters). Boiler is able to produce 180 kWh of energy at one loading of the hard wood
to the feeding chamber (it is ca. 7 hours of operation at full 25 kW output). It correspond to charge of
2 000 l accumulation tank from 20 °C to 90 °C if there is no energy offtake (that is why is necessary to
keep in mind by choosing the size of accumulation tank, that boiler must be operated according to the
size of accumulation tank. It means that, if you have 2000 l tank, load the wood chamber fully. If you
have 1000 l tank, load the chamber halfway – if there is no energy offtake from the accumulation tank). If
the accumulation tank is charged (bottom temperature of the accumulation tank achieves 70 °C) and
boiler achieved set boiler temperature, do not load the wood to the boiler. If you would load the wood to
the boiler in this state, wood would not be combusted (boiler has already achieved set temperature and
fan has turned off). It would get dry and condensates would create in the feeding chamber, what lowers
boiler lifetime. It is necessary to fill the wood at the time when the accumulation tank is almost dis-
charged.
Example 1:
Outside temperature of the environment is −5 °C and heat loss of the object is 10 kW by this tempera-
ture. Boiler has 25 kW at the full output operation. Accumulation tank with volume 2000 l is discharged
(its upper and bottom temperature is 20 °C). The heating system (to cover heat loss) drains 10 kW output
from accumulation tank and boiler has 25 kW output, accumulation tank will be heated by the output of
15 kW – difference between them. 15 kW output makes energy of 105 kWh by full loading of the cham-
ber with hard wood and time of the operation ca. 7 hours. Energy of 105 kWh warms accumulation tank
from 20 °C to 65 °C. It means, that this is the safe economic operation without putting the boiler out of
operation or draining excessive warmth to the waste (boiler was cooled by the aftercooling circuit). Boil-
er is able to cover the heat loss for up to 15 hours at one wood loading.
Example 2:
Outside temperature of the environment is +3 °C and heat loss of the object is 5 kW by this temperature.
Boiler has 25 kW at the full output operation. Accumulation tank with volume 2000 l is discharged (its
upper and bottom temperature is 20 °C). The heating system (to cover heat loss) drains 5 kW output from
accumulation tank and boiler has 25 kW output, accumulation tank will be heated by the output of 20
kW – difference between them. 20 kW output makes energy of 140 kWh by full loading of the chamber
with hard wood and time of the operation ca. 7 hours. Energy of 140 kWh warms accumulation tank from
20 °C to 80 °C. It means, that this is the safe economic operation without putting the boiler out of opera-
tion or draining excessive warmth to the waste. If the heat loss of the object would be constant all the
time – 5 kW, charged accumulation tank would be able to cover heat loss for about 28 h, what is togeth-
er with operation time up to 35 hours without need of wood loading.
That is why it is necessary to keep in mind, that boiler should be loaded only with amount of wood
necessary for charging the accumulation tank, because pointless overheating might lead to putting the
boiler out of the operation or removing excessive warmth to the waste. This is uneconomical and re-
quires activation of the safety element – aftercooling loop.
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ATTACK SLX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ATTACK SLX in the language / languages: English as an attachment in your email.

The manual is 12.12 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of ATTACK SLX

ATTACK SLX Additional guide - English - 21 pages

ATTACK SLX User Manual - German - 112 pages

ATTACK SLX Additional guide - German - 21 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info