[Pc --]Interval of unlock function of circuit pump –when controller is in the stand-by mode or
the room thermostat is disconnected, the circuit pump is started for 30 seconds after each [Pc --]
minutes to prevent the pump blockage caused by its inactivity. The unlock pump function is not
active, when the Pc is set to „- -“.
[ur 0]Operation of the additional output – this parameter defines the operating mode of the
additional output (pump for D.H.W. tank or accumulation tank warming).
[ur 0] Additional output without function – defines that the additional output and pump are
not connected and the additional output is not used in this case.
[ur 1]Priority D.H.W. tank warming – by this setting is the pump for D.H.W. tank warming
connected to the additional output and the sensor of D.H.W. is connected to the additional
inlet.Then, if the temperature in the D.H.W. tank decreases under the value of hysteresis
[uh 5] from the temperature adjusted[u 60], the pump of D.H.W. tank warming is started. After
the temperature in the D.H.W. tank reaches the set value [u 60], the pump is stopped. The pump
is also stopped, when the temperature in boiler is lower than the temperature in D.H.W. tank.
The [ur 1] mode means that the D.H.W. warming has priority, i.e. the pump of the heating circuit
is started after the D.H.W. is prepared.
[ur 2] Parallel charging the D.H.W. tanksimilar principle as by the[ur 1], just the D.H.W. is
prepared by the parallel operation of the circuit pump of the heating circuit.
[ur 3]Unused
[ur 4]Charging the accumulation tank – due to this setting is the additional output used as
a pump to heat the accumulation tank and the additional sensor measures its temperature.
When the temperature in the boiler exceeds the hysteresis [uh 5] over the current temperature
of accumulation tank, the pump for charging is started. The pump is stopped, when the
temperature in the boiler is same or lower than the temperature in the accumulation tank, or
when the temperature in boiler decreases under the minimum boiler temperature defined by
the parameter [L 65].
[u 30] Operating temperature of the D.H.W. tank or accumulation tank – temperature to
control the additional output [ur ].
[uh 5]Hysteresis of the D.H.W. tank or accumulation – this parameter defines hysteresis of the
additional output [ur ].
[uP 5]Boiler temperature increase by D.H.W. preparation – this parameter is relevant, when
the additional output works under the mode of D.H.W. tank charging. It defines, for how many
degrees will the adjusted boiler temperature be higher than parameter [u 50]during the D.H.W.
tank warming.
[L 65]Minimum boiler temperature – defines the minimum boiler temperature that can be set
by a knob.
[H 85]Maximum boiler temperature – defines the maximum boiler temperature that can be
set by a knob.
[h2] Hysteresis of boiler temperature – defines the difference between the adjusted and the
current boiler temperature for which must the boiler temperature decrease to start the
controller again after the adjusted boiler temperature is achieved.
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ATTACK DPX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ATTACK DPX in the language / languages: English as an attachment in your email.

The manual is 11.03 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of ATTACK DPX

ATTACK DPX Additional guide - English - 21 pages

ATTACK DPX Additional guide - German - 21 pages

ATTACK DPX User Manual - German - 48 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info