12 - GB
Operation Manual - GB
7. Type of environment and location of the boiler with the
burner in the boiler room
Boilers with a pellet burner may be used in the AA5/AB5 basic environment in accordance with
the ČSN3320001 standard. Boilers must be installed in a boiler room with guaranteed sufficient sup-
ply of combustion air. It is unacceptable to locate boilers on residential premises (incl. corridors). The
cross-section of the opening
for supply of combustion air
to the boiler room must be at
least 350 cm
2
for boilers with
an output of 15 - 45 kW.
1. Chimney
2. Flue gas duct
3. Boiler
4. A25 burner
5. External conveyor
6. Bin (500 l)
8. Chimney
A boiler with a burner must always be connected to the chimney vent with consent of the
responsible chimney maintenance company. The chimney vent must always produce sufficient
draught and exhaust flue gas to the free atmosphere in virtually all operation conditions. For proper
function of boiler the separate chimney vent must be properly dimensioned as the combustion, out-
put and service life of the boiler depends on its draught. The draught of a boiler directly depends
on its cross-section, height and roughness of the inner wall. No other device may be connected to the
chimney to which a boiler is connected. The diameter of the chimney must not be smaller than the
outlet on the boiler (min. 150 mm). The chimney draught must achieve prescribed values (see the
technical specifications in the boiler manual). However, the boiler must not be excessively high so as
not to reduce the efficiency of the boiler and not to disturb its combustion (tear the flame). In case of
too strong draught install a throttling flap or draught reducer in the flue gas duct between the boiler
and the chimney.
Guideline values of dimensions of the chimney cross-section:
20 x 20 cm height 7 m
Ø 20 cm height 8 m
15x15cm height 11 m
Ø 16 cm height 12 m
The exact determination of chimney dimensions is defined by the ČSN 73 4201 standard.
The prescribed chimney draught is specified in the “Technical data” chapter of the manual of the
particular boiler.
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos D25P at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos D25P in the language / languages: English as an attachment in your email.

The manual is 1,52 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info