Operation and Maintenance Manual - EN
EN
www.atmos.cz EN-43
Parameter S66 - characterizes run-out time of the burner in OPERATION mode during which the
burner stays in operation when waste gas temperature in the heat exchanger of the boiler descend
under the temperature characterized by the parameter S64.
After the time characterized by the paramater S66 is display ALARM PELLETS – REFILL
PELLETS. In this case check the pellet tank and fill up the fuel.
DxxPX (PXxx) boilers are designed that after fuel refill is neccesary only to turn off and on the
main swich on the boiler. So it is not neccesary fill up the pellets into the conveyor after showen
ALARM PELLETS – REFILL PELLETS.
Function is only for DxxPX (PXxx) boilers, burner profile A25PX. Do not change… (30 min)
• Parameter S67 - characterizes function of R5 reserve output similar with S6 and S14 parameters
with instaled AC07X-C additional module. Primary is this reserve used to control air pump for
pellet burner pneumatic ash cleaning system.... (15).
Function is also for DxxPX (PXxx) boilers, burner profile A25PX (A25PX pneu)
if:
a) S67 = 1…. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be closed and the reserve output will be energized. Thanks to this you can start a spare source
of energy for heating of the building as e.g. a gas, electric or oil boiler.
b) S67 = 2….. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be opened and the reserve output will not be energized. Thanks to this a signal can be sent to
an electrically backed up AB01 ATMOS GSM module controller that will send information that
there is a system fault or the system is not energized. This is the opposite logic (to S6 = 1), which
means that during normal operation the reserve is energized.
c) S67 = 4…… The reserve function as the reversed function of the output for the burner fan,
when the reserve output is off, is not energized always when the burner fan is running. This
function is always activated if you connect the A25 burner with the AS25 set containing the
AD02 or AD03 module, which in this case controls the extraction fan of the boiler. Install the
AD02 or AD03 module under the instrument hood of the boiler and connect it electrically
between the boiler terminal board and the extraction fan, see the wiring diagram.
This setting and connection with AD02 or AD03 module and special connector (jumper to main
switch) is standardly used for DCxxSP boilers with the function for automatic start after
wood is burnt out activated (AUTOSTART - S34 = 1 or S34 = 2). Boiler exhaust fan is run-
ning simultaneously with the pellet burner during the AUTOSTART function.
d S67 = 7….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve output work independently of the condition of the actual output for the external worm
conveyor. This means that if the standard output for the external conveyor gets damaged, the re-
serve will work independently in accordance with the same program, and therefore it can be used
as a replacement for the damaged output.
e) S67 = 8….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
43


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A85 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A85 in the language / languages: English as an attachment in your email.

The manual is 2.45 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Atmos A85

Atmos A85 User Manual - German - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info