810412
41
Zoom out
Zoom in
Previous page
1/66
Next page
Operation and Maintenance Manual - EN
EN
www.atmos.cz EN-41
• Parameter S54 - characterizes TEMPERATURE D in the applications of function S14 = 25 to
36…. (75 °C)
This is a free function for the reserve output R2 (R6) on the first position (Temperature D = second
position in function S14 = 25 to 36 (S68 = 17 až 36)).
• Parameter S55 - characterizes the activation or deactivation difference for TEMPERATURE D
in the applications of function S14 = 25 to 36… (5K)
This is the difference for the free function of reserve output R2 (R6) on the second position
(difference for Temperature D = difference for the second position in the function S14 = 25 to 36
(S68 = 17 až 36)).
Parameter S56 - characterizes control of functioning (speed sensing) of the exhaust blower of
the boiler (blower 2); setting may be different according to use – must never be changed...... (1)
a) S56 = 0 ..... control of the exhaust blower of the boiler turned off
a) S56 = 1 ..... control of the exhaust blower of the boiler turned on
If S56 = 1, parameters S47 and S57 are activated (visualized).
Parameter S57 - characterizes minimum speed of the blower 2 ....... (1500 rpm) must never
be changed
adjustable range..... 1000 – 3200 rpm
It is a function of the control of proper functioning of the exhaust blower of the boiler.
When the blower is running at the speed lower than set, “ALARM VENT 2” is declared.
This function is not used standardly.
• Parameter S58 - characterizes the amount of compressed air for the first pre-cleaningoftheburner
when installing pneumatic cleaning the burner. This is the time at which the partial fillingcompressor
air tank for pre-cleaning of the burner ... (10 s) - standardly do not change
Adjustable range...OFF, 1 - 120 s.
Parameter S59 - characterizes the amount of compressed air for the second pre-cleaning of the
burner when installing pneumatic burner cleaning. This is the time at which the partial filling
compressor air tank for pre-cleaning of the burner... (20 s) - standardly do not change
Adjustable range...OFF, 1 - 120 s.
Parameter S60 - characterizes the amount of compressed air for the third pre-cleaning of the
burner when installing pneumatic burner cleaning. This is the time at which the partial filling
compressor air tank for pre-cleaning of the burner... (30 s) - standardly do not change
Adjustable range...OFF, 1 - 120 s.
• Parameter S61 - characterizes the function for control of the boiler exhaust fan from the outlet for
the burner discharge fan via the AD04 module. The function is intended for models DCxxSP(X),
CxxSP, ACxxSP without flap with actuator fitted with the pneumatic burner cleaning options and the
activated function for automatic start of the burner following wood burnout - AUTOSTART... (0)
a) S61 = 0....... function OFF
b) S61 = 1....... function ON (for for profile A25 pneu)
Never activate this function for boilers DCxxGSP and DCxxSP(X), CxxSP, ACxxSP (Model 2018
equipped with flap with actuator).
41


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A85 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A85 in the language / languages: English as an attachment in your email.

The manual is 2.45 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Atmos A85

Atmos A85 User Manual - German - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info