• Parameter S68 - characterizes function of R6 reserve output similar with S6 and S14 parameters
with instaled AC07X-C additional module. Primary is this reserve used to control air pump for
pellet burner pneumatic ash cleaning system S68 = 16.
Function is only for DC40GSP and DC40SPT boilers or burners equiped with additional module
AC07X-C, burner profile A45GSP (A45GSP pneu) and A45SP (A45SP pneu)....... (0)
if:
a) S68 = 1… If any fault occurs in the burner and the burner is shut down, the reserve relay will
be closed and the reserve output will be energized. Thanks to this you can start a spare source
of energy for heating of the building as e.g. a gas, electric or oil boiler.
b) S68 = 2… If any fault occurs in the burner and the burner is shut down, the reserve relay will
be opened and the reserve output will not be energized. As a result, we can send a signal to an
electrically backed -up device (GSM, WiFi, ...), which sends information that the device has fallen
into a fault or is not under current. This is the opposite logic (to S68 = 1), which means that
during normal operation the reserve is energized.
c) S68 = 3… The reserve function as the output function for the burner fan, when the reserve
output is closed, is energized always when the burner fan is running (fan mode only 100 % or
OFF). This function is applied if you want the boiler fan or extraction fan in the chimney to run
together with the burner fan. This function is designed for direct control of an fan directly from
the burner (e.g. DxxPX, PXxx).
d) S68 = 9… Reserve function as the output function for the external worm conveyor, when the
reserve copies the run of the external worm conveyor, but with the difference that it does not cycle,
but runs permanently both during the drawing of the ignition amount and during both the
times T4 and T6. Thus, the other external conveyor runs continuously and works independently
of the status of the actual output for the external worm conveyor. This means that if the output
to the main external conveyor from which pellets directly fall to the burner gets damaged, the
reserve will keep working independently. This function can be used in cases when you need to
control another external conveyor that supplies (feeds) pellets from a larger distance to a pellet
bin at the boiler from which the main external conveyor draws pellets to supply them directly to
the burner. Caution - the other external conveyor must always be controlled with an additional
level sensor (level meter) that will maintain the level of pellets in the pellet bin at the boiler.
e) S68 = 10….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor, but with the difference that it does not
cycle, but runs permanently both during the drawing of the ignition amount and during
both the times T4 and T6. Thus, the other external conveyor runs continuously, but it works in
dependence on the status of the actual output for the external worm conveyor. This means that if
the output for the external conveyor from which pellets fall directly to the burner gets damaged,
the reserve will be switched off automatically. This function is convenient in cases when you
need to control another external conveyor that supplies (feeds) pellets from a larger distance to
a pellet bin at the boiler from which the main external conveyor draws pellets to supply them
directly to the burner. Caution - the other external conveyor must always be controlled with an
additional level sensor (level meter) that will maintain the level of pellets in the pellet bin at the
boiler. This is a similar function to S68 = 9, but with a higher degree of safety.
51


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A45SPT at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A45SPT in the language / languages: English as an attachment in your email.

The manual is 6.79 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info