Operation and Maintenance Manual - EN
d S67 = 7… Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve output work independently of the condition of the actual output for the external worm
conveyor. This means that if the standard output for the external conveyor gets damaged, the
reserve will work independently in accordance with the same program, and therefore it can be
used as a replacement for the damaged output.
e) S67 = 8… Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve works in dependence on the status of the actual output for the external worm conveyor.
This means that if the output for the external conveyor gets damaged, the reserve will be switched
off automatically. This function is suitable in situations when you need to control another external
conveyor that supplies (feeds) pellets from a larger distance to the main conveyor from which the
pellets fall directly to the burner.
f) S67 = 15… Reserve function for the compressor control during the function for automatic
burner cleaning using compressed air. Power element designed for switching and powering the
compressor (e.g. contactor) must be connected between reserve output R5 and the compressor.
This function is connected with S68, S41, S42, S43, S44, S45, S46, S47 parameter, which must be
checked and configured.
g) S67 = 16… Reserve function for controlling el.fan during the function for automatic burner
cleaning using compressed air. This function is connected with S68, S41, S42, S43, S44, S45, S46,
S47 parameter, which must be checked and configured.
Special function for turning on reserve output R5 according to the temperature of a concrete sensor:
a) e.g. function: TS>……. means that if the TS sensor temperature is higher then the set value in
S48 parameter – Temperature A, reserve output R5 will be activated
b) e.g. function: TS<……. means that if the TS sensor temperature is higher then the set value in
S48 parameter – Temperature A, reserve output R5 will be deactivated
c) e.g. function: TS,TV>… means that if the TS and TV sensor temperature is higher at the same
time then the set value in S48 parameter – Temperature A and S50 – Temperature B, reserve output
R5 will be activated (Temperature A = first position (TS), Temperature B = second position (Tv)).
d) e.g. function: TS,TK<… means that if the TS and TK sensor temperature is higher at the same
time then the set value in S48 parameter – Temperature A and S50 – Temperature B, reserve output
R5 will be deactivated (Temperature A = first position (TS), Temperature B = second position (Tk)).
Individual functions:
(17) TS>
(18) TS<
(19) TV>
(20) TV<
(21) TK>
(22) TK<
(23) TSV>
(24) TSV<
(25) TS,TV>
(26) TS,TV<
(27) TS,TK>
(28) TS,TK<
(29) TS,TSV>
(30) TS,TSV<
(31) TV,TK>
(32) TV,TK<
(33) TV,TSV>
(34) TV,TSV<
(35) TK,TSV>
(36) TK,TSV<
50


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A45SPT at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A45SPT in the language / languages: English as an attachment in your email.

The manual is 6.79 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info