Operation and Maintenance Manual - EN
f) S6 = 6….. Cleaning function of the combustion chamber or grill (flap). If the burner is in the
normal START, RUN and STOP mode, the output is not energized. The output is only energized
for the limited time T11, which continues immediately after the expiration of time T5 in the
STOP mode. It is not used with the A45 burner.
g) S6 = 7….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve output work independently of the condition of the actual output for the external worm
conveyor. This means that if the standard output for the external conveyor gets damaged, the
reserve will work independently in accordance with the same program, and therefore it can be
used as a replacement for the damaged output.
h) S6 = 8….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve works in dependence on the status of the actual output for the external worm conveyor.
This means that if the output for the external conveyor gets damaged, the reserve will be switched
off automatically. This function is suitable in situations when you need to control another external
conveyor that supplies (feeds) pellets from a larger distance to the main conveyor from which the
pellets fall directly to the burner.
i) S6 = 9….. Reserve function as the output function for the external worm conveyor, when the
reserve copies the run of the external worm conveyor, but with the difference that it does not cycle,
but runs permanently both during the drawing of the ignition amount and during both the
times T4 and T6. Thus, the other external conveyor runs continuously and works independently
of the status of the actual output for the external worm conveyor. This means that if the output
to the main external conveyor from which pellets directly fall to the burner gets damaged, the
reserve will keep working independently. This function can be used in cases when you need to
control another external conveyor that supplies (feeds) pellets from a larger distance to a pellet
bin at the boiler from which the main external conveyor draws pellets to supply them directly to
the burner. Caution - the other external conveyor must always be controlled with an additional
level sensor (level meter) that will maintain the level of pellets in the pellet bin at the boiler.
j) S6 = 10….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor, but with the difference that it does not
cycle, but runs permanently both during the drawing of the ignition amount and during
both the times T4 and T6. Thus, the other external conveyor runs continuously, but it works in
dependence on the status of the actual output for the external worm conveyor. This means that if
the output for the external conveyor from which pellets fall directly to the burner gets damaged,
the reserve will be switched off automatically. This function is convenient in cases when you
need to control another external conveyor that supplies (feeds) pellets from a larger distance to
a pellet bin at the boiler from which the main external conveyor draws pellets to supply them
directly to the burner. Caution - the other external conveyor must always be controlled with an
additional level sensor (level meter) that will maintain the level of pellets in the pellet bin at the
boiler. This is a similar function to S6 = 9, but with a higher degree of safety.
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A45SPT at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A45SPT in the language / languages: English as an attachment in your email.

The manual is 6.79 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info