9. TROUBLESHOOTING GUIDE.
The reasons why your dehumidifier may not function properly are mentioned below:
The unit does not start:
Open switch: Check that there is not open circuit and repair if it is needed.
Coil contactor does not activate: Verify that it is not burned, and replace it if it is. Verify the terminals which
activate the coil.
Internal thermal switch tripped: Verify the voltage of the line. Verify that the operating conditions are correct.
Excessive compressor consumption. Short circuit in the compressor.
Low pressure switch tripped: Verify the switch operates correctly, replacing it if necessary. Verify that the fan
is operating correctly. Verify the refrigerant charge of the equipment (refrigerant leak, loss of refrigerant fluids) in
order to solve this problem; please refer to the refrigerant charge section. Verify that there is sufficient
ventilation around coils: Verify that there are no obstructions in the cooling circuit and eliminate them if there
are. Verify that the switch wires function properly and replace them if necessary.
High pressure switch tripped: Verify that the pressure switch operates correctly and substitute if necessary.
Check the refrigerant charge (excess refrigerant) in order to solve this please refer to the refrigerant charge
section. Check for any obstruction of the cooling circuit and eliminate the obstruction if necessary. Check that
the water is circulating through the condenser without any obstructions, that the valves are oponed and the
pump it is working OK (substitute if it is needed).
Flow alarm: Check that the debugger pump works correctly (flow is according to the specs). Clean the filter if
needed and check that the by-pass valves are OK. If the pump is not debugging check the time set and the
operation mode. If finally the flow switch is out of order contact the Technical service for assistance
Defrost cycle: The ambient conditions are not correct (temperatures are too low). The machine will not operate
under these conditions; in this case, the regulator will affect the condenser, shutting it off until the ambient
temperature returns to the minimum required limits for correct operation.
Low oil level:
Low oil level : Complete until reach the specified.
Oil stains on the equipment: Check for leaks in the cooling circuit and repair them if necessary, check the
torque on the high and low mini pressure switches, and replace them if necessary.
The equipment operates on cycles which are too short:
The low pressure switch opens then closes again: Verify the points mentioned in the "low pressure switch
tripped" section above.
Intermittent contact on machine control unit: Repair or replace the faulty electrical part. Check the
Temperature control unit
Make sure the equipment is not too large for the facilities.
The equipment does not shut down:
Verify that the humidistat functions properly: repairing or replacing it if necessary.
Compressor contactor contacts are stuck together: Check that the coil is functioning properly and that the
contacts are not burned.
The pressure of the intake duct is too low: Check the refrigerant charge of the equipment for leaks, to solve
this problem please refer to the refrigerant charge section. Check that there are no obstructions in the cooling
circuit, lines, etc. and replace if necessary.
Verify that the equipment is powerful enough for the existing thermal conditions.
Excessive noise:
The fastening screws of the compressor or fan are loose: Tighten all the fastening elements.
Check the compressor oil level.
The compressor produces internal bumping noises: Check that the noise does not come from any fluid leak
from overheating (see section of refrigerant charge).
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Astralpool OPTIMA 15 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Astralpool OPTIMA 15 in the language / languages: English, Portuguese, Spanish as an attachment in your email.

The manual is 1,93 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info