COMPRESSOR
COMPRESSORCOMPRESSOR
COMPRESSOR
Compressor oil must be checked in those unit models provided with an oil viewer.
Verify that the compressor refrigerates adequately with the circulating gas (verify the
refrigerant charge).
Verify that the power consumption has not increased.
Verify that the compressor discharge pressure is not too high and that the intake pressure is not
too low.
Verify that the compressor fasteners are not deteriorated.
Verify that no frost develops on the compressor.
CONDENSER
CONDENSERCONDENSER
CONDENSER
Install chemical feeders “downstream” from the heat pump, as far away and at a lower height.
The feeder should never be installed near the intake of the purification pump as this will
damage the condenser.
NEVER introduce concentrated chemical products in the pool skimmers as this will damage the
Titanium condenser.
In climates where temperatures occasionally fall below freezing, circulate the water using the
purification pump to maintain the water temperature above freezing (32º F).
In the case these temperatures are persistent or habitual, the heating and purification system
should be completely drained. The condenser has a lateral plug the purge the system.
FAN
FANFAN
FAN
Verify the flows of the fan each year.
Clean the louvers of the fan as well as the protection grill regularly.
ELECTRICAL PANEL
ELECTRICAL PANELELECTRICAL PANEL
ELECTRICAL PANEL
Verify all electrical connections.
Verify that there is no over-heating of the electrical terminals.
Verify that the protection systems operate correctly.
Verify that the regulator operates correctly and verify the temperature with a mercury
thermometer (calibration probe).
9.
9. 9.
9. REFRIGERANT CHARGE
REFRIGERANT CHARGEREFRIGERANT CHARGE
REFRIGERANT CHARGE
For the procedures described below, we recommend you contact a professional specialised in
heating and air conditioning units.
DRAINING THE COOLING CIRCUIT
DRAINING THE COOLING CIRCUITDRAINING THE COOLING CIRCUIT
DRAINING THE COOLING CIRCUIT
It is imperative to drain the cooling circuit before charging the refrigerant.
First draining procedure:
Connect the gauge tubes to the intake pressure lines of the circuit (low pressure) and to
the return pressure lines (high pressure).
Connect the main line of the gauge to the vacuum pump.
Open all the valves, including the solenoid and the regulating valves.
Open the valves of the gauge (LO = low pressure valve / HI = high pressure valve).
Activate the vacuum pump and wait until the circuit is completely drained.
Close all valves or stopcocks and disconnect the vacuum pump.
REFRIGERANT GAS CHARGE
REFRIGERANT GAS CHARGEREFRIGERANT GAS CHARGE
REFRIGERANT GAS CHARGE
The equipment uses R-407C class refrigerant.
This is the reason why the gas taken from the refrigerant bottle must be introduced in the low-
pressure circuit by means of a charger (expansion system).
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Astralpool ASTRALPOOL HEAT II at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Astralpool ASTRALPOOL HEAT II in the language / languages: English, German, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 8,54 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info